1500 KVA Masu Canzawa Akwatin Lantarki-4.16 / 0.48 KV|Amurka 2025
Yawan aiki: 1500 kVA
Ƙarfin wutar lantarki: 4.16D-0.48Y/0.277 kV
Feature: tare da bawul na Schrader

Pad{0}Mounted Transformers: Matsayin Zamani don Rarraba Ƙarfi.
01 Gabaɗaya
1.1 Bayanin Aikin
1000 kVA uku fage pad mounted transformer an isar da ita zuwa Amurka a shekarar 2024. Ƙarfin wutar lantarkin shine 1500 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 4.16D kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.48Y / 0.277 kV, sun kafa ƙungiyar vector na Dyn1.
An ƙera shi don dogaro da aminci a cibiyoyin rarraba wutar lantarki, Pad ɗin mu{0}Mounted Transformer shine ginshiƙin tsarin wutar lantarki na ƙasa na zamani. An ƙera shi don haɗa kai cikin wuraren zama, kasuwanci, da masana'antu, yana ba da aiki mai ƙarfi yayin ba da fifikon amincin jama'a da sanin yakamata.
Muhimmin fasalin da ke ba da gudummawa ga dorewar sa na musamman da kuma dorewar dogon lokaci shine amfani da manyan bushings na pocelain mai ƙarfi. Shahararru don ƙarfin injin su mafi inganci, kyawawan kayan aikin wutan lantarki, da tabbataccen juriya ga lalata muhalli, waɗannan ɓangarorin ɓangarorin suna tabbatar da amintaccen wurin haɗin gwiwa don matsakaici{3}} igiyoyin wutar lantarki. Ƙarfin gininsu yana ba da kyakkyawan aiki a ƙarƙashin maɓalli daban-daban na zafi da na lantarki, yana ba da tabbacin aminci cikin shekaru da yawa na sabis.
An lulluɓe shi a cikin madaidaicin tamper{0}}, shingen ƙarfe na kulle, wannan tafsiri yana haɗa mafi kyawun aiki na lokaci{1}}kayan da aka gwada kamar porcelain tare da ci-gaba na cibiya da fasahar coil. Yana tsaye a matsayin amintaccen, ƙananan bayanan martaba, kuma ingantaccen abin dogaro don saukar da wuta cikin inganci daga grid mai amfani zuwa ƙarshen mai amfani-.
1.2 Ƙayyadaddun Fasaha
1500 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Amurka
|
|
Shekara
2024
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE Std C57.12.34-2022
|
|
Ƙarfin Ƙarfi
1500 kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
4.16d kV
|
|
Na biyu Voltage
0.48Y/0.277 kV
|
|
Abubuwan Iska
Aluminum
|
|
Ƙungiyar Vector
Dyn1
|
|
Impedance
5.75%
|
|
inganci
99.48%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
1.545 kW
|
|
Akan Rasa Load
10.54 kW
|
1.3 Zane
1500 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori

Mahimmancin mu yana rage rashin asarar kaya da kashi 70 cikin 100, yana isar da matsakaicin tanadin makamashi da ƙananan farashin rayuwa don ROI mafi girma. An gina shi don dogaro da aiki mai natsuwa, shine mafi wayo na dogon lokaci{3}} saka hannun jari.
2.2 Guda
Mu kushin da aka ɗora masu taswira sun ƙunshi amintattun HV foil na aluminum da wiwi na LV na waya. Wannan ƙira yana tabbatar da ƙaƙƙarfan ƙaƙƙarfan ƙarfin kewayawa da aikin zafi, yana ba ku mafi girman lokacin aiki akan ƙaramin farashi fiye da madadin jan ƙarfe.

2.3 Tanko

Tankin mu an yi shi da ƙarfe maras sumul, lalata{0}}ƙarfe, an gwada shi sosai don tabbatar da hatimin ɗigo{1} na rayuwa. Wannan yana kawar da damuwa na kulawa da tsaftace muhalli mai tsada, yana samar da cikakken aminci da ƙarancin farashi na dogon lokaci-.
2.4 Taron Karshe
Haɗin ƙarshe na pad ɗin mu{0}masu tafsiri yana haɗe da cibiya, coils, da tanki tare da daidaitaccen tsari da ingantattun matakai. Wannan yana tabbatar da ingantacciyar aiki, ƙarancin hayaniya da rawar jiki, da ingantaccen tsarin lokaci mai tsawo{2}. Kuna karɓar na'ura mai canzawa wanda ke aiki cikin nutsuwa kuma amintacce daga rana ta ɗaya, tare da goyan bayan ingantattun sarrafa ingancin mu da ƙwarewar filin mu.

03 Gwaji
Don 1500kVA na mu guda uku{1}} pad{2}} wanda aka ɗora tasfoma (4160Δ{12}}480Y/277V), gwaji yana mai da hankali kan abubuwan da kuka fi dacewa: farashi mai rahusa, babu raguwa. Muna raba bayyanannun bayanai: 2.83% rashin daidaituwa na iska (yana guje wa zafi mai zafi), -0.23% ~ 0.15% jujjuya rabo (ikon barga), 18.2-18.6GΩ rufi (ƙananan laifuffuka), 12h yatsa-kyau (ba farashin mai), 56.4kV mai ƙarfi (aiki lafiya), da 8% effici.s. Duk ma'auni sun cika garanti.
|
A'a. |
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
2.83 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
-0.12 |
Wuce |
|
3 |
Mataki{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% |
I0 :: bayar da ma'auni darajar |
0.26 |
Wuce |
|
kW |
P0: bayar da ma'auni (digiri 20) |
1.567 |
|||
|
/ |
Haƙuri don asarar nauyi shine ± 10% |
/ |
|||
|
5 |
Load asarar , impedance ƙarfin lantarki, jimlar asara da kuma yadda ya dace |
/ |
t:85 ku haƙuri ga impedance shine ± 7.5% Haƙuri don asarar nauyi shine ± 6% |
/ |
Wuce |
|
% |
Z%: ƙimar da aka auna |
5.67 |
|||
|
kW |
Pk: ƙimar ƙima |
10.475 |
|||
|
kW |
Pt: ƙima mai ƙima |
12.042 |
|||
|
% |
Ingancin ba kasa da 99.48% |
99.48 |
|||
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
HV: 19kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 0.96 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Kasa: |
18.2 |
/ |
|
LV -HV zuwa Ground: |
18.6 |
||||
|
HV&LV zuwa Ground: |
18.5 |
||||
|
9 |
Gwajin Leaka |
/ |
matsa lamba: 20kPA |
Babu yabo kuma babu Lalacewa |
Wuce |
|
Tsawon lokaci: 12h |
|||||
|
10 |
Gwajin Mai |
kV |
Ƙarfin Dielectric |
56.4 |
Wuce |
|
mg/kg |
Abubuwan Danshi |
9.9 |
|||
|
% |
Factor Dissipation |
0.00247 |
|||
|
mg/kg |
Furan Analysis |
/ |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Shiryawa da jigilar kaya
4.1 Shiryawa

Pad ɗin mu guda uku{0}}{1}masu tafsirin na'ura suna amfani da kariyar dual: vacuum na farko - an rufe su a cikin jakunkuna na foil na aluminum tare da kayan bushewa (tsatsawar tsatsa, al'amuran gama-gari masu fafatawa suna watsi da su), sannan an nannade su da masu kariyar kusurwa kuma an cushe cikin akwatunan katako masu ƙarfi. Ba kamar sauran akwatunan da ba a yiwa alama ba, namu yana da forklift/cibiyar{4}}na{5}} labulen nauyi don sauƙin mu'amala{6}} yana tabbatar da cewa taranfoma ta zo daidai, a shirye don amfani.
4.2 Shipping
A ƙarƙashin sharuɗɗan CIF ɗin mu zuwa tashar jiragen ruwa na Los Angeles, muna ɗaukar cikakken alhakin farashi, inshora, da jigilar kaya. Haɗin gwiwarmu tare da manyan dillalai masu ɗaukar nauyi da ƙwararrun tsare-tsare na dabaru suna tabbatar da cewa taswirar ku ta zo kan lokaci kuma cikin cikakkiyar yanayi. Wannan yana kawar da sarƙaƙƙiya da haɗari na jigilar kaya na ƙasa da ƙasa a gare ku, yana ba da tabbacin farashi da kwanciyar hankali.

05 Yanar Gizo da Takaitawa
Lokacin da ka ƙididdige na'urorin mu guda uku - ɗorawa masu tasfofi, kuna zaɓar fiye da samfur kawai - kuna saka hannun jari a cikin shekarun da suka gabata na ingantaccen aiki. Daga ƙaƙƙarfan iska mai ƙarfi na aluminium da yoyon tanki{2} zuwa amintaccen marufi da isar da sarrafawa, kowane dalla-dalla an ƙirƙira shi don rage farashin rayuwar ku da haɗarin aiki. Muna isar da ingantaccen abin dogaro wanda ke kiyaye ayyukan ku akan jadawali da ƙarfin al'ummar ku, kowace shekara.

Hot Tags: akwatunan lantarki na lantarki, masana'anta, mai kaya, farashi, farashi
You Might Also Like
225 kVA Kushin Dutsen Mai Canjawa-34.5 / 0.208 kV|Am...
2500 kVA Padmounted Transformers-24.94 / 0.6 kV|Kana...
3000 kVA Pad Transformers-23 / 0.38 kV|Salvador 2025
300 kVA Kushin Haɗa Mai Canjawa-12 / 0.208 kV|Jamaic...
750 kVA Kushin Dutsen Mai Canjawa-25 / 0.6 kV|Kanada...
2000 kVA Kushin Haɓaka Mai Rarraba Rarraba-4.16/0.08...
Aika Aikace-aikacen