500 kVA Utility Pad Hawan Canji-24 / 0.48 kV|Amurka 2024

500 kVA Utility Pad Hawan Canji-24 / 0.48 kV|Amurka 2024

Ƙasar Bayarwa: Amurka 2024
Yawan aiki: 500kVA
Wutar lantarki: 24000 D-480Y/277 V
fasali: tare da ciyarwa -ta hanyar sakawa
Aika Aikace-aikacen

 

 

500 kva utility pad mounted transformer-inside-view

Ƙaddamar da aminci tare da aminci, inganci, da ɗorewa- Scotech pad{1} da aka ɗora tafsirin da aka gina don buƙatun makamashi na yau.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

500 kVA guda uku -saitin kushin{2}} wanda aka ɗora tafsiri, wanda aka kawo zuwa Amurka a cikin 2024, an ƙera shi don saduwa da ƙa'idodin inganci na IEEE Std C57.12.34-2022 da DOE 2016.

Yana aiki a 60 Hz, yana da babban ƙarfin lantarki na farko na 24 kV da ƙarfin lantarki na biyu na 480GrdY/277 V tare da ƙungiyar Dyn1 vector. Theutility kushin saka taransifomayana amfani da iskar tagulla da sanyaya KNAN, cike da man ester na halitta na FR3 don ingantacciyar lafiyar wuta da kiyaye muhalli. Ya haɗa da damar ciyarwar madauki, mataccen damar shiga gaba, da babu{3}}mai sauya matsa lamba tare da kewayon daidaita wutar lantarki ±2 × 2.5%. Tare da rashin ƙarfi na 5.75%, babu-asara na 0.610 kW, kuma akan - asarar 4.530 kW, wannan rukunin yana ba da ingantaccen matsakaicin matsakaici mai inganci{12}} rarraba wutar lantarki. Yana da kyau a yi amfani da shi a cikin rukunin kasuwanci, ƙananan wuraren masana'antu, da ci gaban zama inda ake buƙatar canji mai aminci, daidaito da inganci.

 

 

 

1.2 Ƙayyadaddun Fasaha

500kVA kushin mai amfani da aka ɗora ƙayyadaddun kayan wuta da takaddar bayanai

Isarwa zuwa
Amurka
Shekara
2024
Nau'in
Uku fanni kushin Dutsen transformer
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
500 kVA
Yawanci
60HZ
Ciyarwa
Madauki
Gaba
Matattu
Mataki
Uku
Nau'in Sanyi
KNAN
Liquid insulant
Farashin FR3
Babban Voltage
24 kv
Na biyu Voltage
0.48 kV
Ƙungiyar Vector
Dyn1
Abubuwan Iska
Copper
Impedance
5.75%
Ƙimar inganci da hasara
DOE 2016
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.610 kW
Akan Rasa Load
4.530 kW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

 

1.3 Zane

500kVA mai amfani da kushin da aka ɗora taswira zane da farantin suna

500 kva utility pad mounted transformer-outline-drawing 500 kva utility pad mounted transformer-nameplate

 

 

02 Masana'antu

2.1 Kori

Ana yin muryoyin wutar lantarki na SCOTECH daga ƙarfen siliki mai birgima mai girma{0}}saho da aka shigo da shi{1}. Yin amfani da in{3}}madaidaicin layin gida, ana sarrafa burrs a ƙasa da 0.02 mm. Ƙaƙƙarfan maɓalli suna da cikakkun mahaɗaɗɗen haɗin gwiwa ba tare da naushi ko ruɓaɓɓen karkiya ba, haɓaka aikin maganadisu da rage asarar kuzari.

500 kva utility pad mounted transformer-steel-core

 

2.2 Guda

500 kva utility pad mounted transformer-copper-foil-windings

Wannan 500 kVA mai taswira yana fasalta iskar jan ƙarfe ko aluminium a gefen LV, yana ba da ko da rarrabawa na yanzu da ƙaƙƙarfan juriya na kewayawa-. Gefen HV na amfani da enamel{3}}waya mai rufi a cikin tsari mai yawa{4}}, yana samar da ingantaccen rufi da ingantaccen aiki a 24 kV.

 

2.3 Tanko

Tankin transfoma wani tsari ne na ƙarfe da aka rufe wanda ke da gida mai mahimmanci, iska, da mai. An tsara shi don ƙarfi da karko, yana kare abubuwan ciki daga danshi, gurɓataccen abu, da lalata injiniyoyi, yana tabbatar da aiki mai aminci da tsawon rayuwar sabis.

500 kva utility pad mounted transformer-sealed steel transformer tank

 

2.4 Taron Karshe

500 kva utility pad mounted transformer-front-door-open

Scotech yana amfani da manyan suturar ɗorewa - ga duk saman taswira. Bayan shigarwa da tsaftacewa, duk wani ɓarna ko ƙarewar lalacewa ya kamata a taɓa ta ta amfani da fenti mai dacewa da Scotech aka bayar ko ƙayyadaddun, yana kiyaye juriyar lalata da daidaiton kyan gani.

 

 

03 Gwaji

Gwajin Na yau da kullun da Matsayin Gwaji

1. Ma'aunin Juriya bisa ga IEEE C57.12.90-2021 Sashe na 5

2. Mataki na -Gwajin dangantaka bisa ga IEEE C57.12.90-2021 Sashe na 6

3. Gwajin Ratio bisa ga IEEE C57.12.90-2021 Sashe na 7

4. Babu Asara Load kuma Babu Load A halin yanzu bisa ga IEEE C57.12.90-2021 Sashe na 8

5. Haɓaka Load, Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarfafawa bisa ga IEEE C57.12.90-2021 Sashe na 9

6. Gwajin Juriya da Wutar Lantarki bisa ga IEEE C57.12.90-2021 Sashe na 10.5.1

7. Gwajin Ƙarfin Wutar Lantarki bisa ga IEEE C57.12.90-2021 Sashe na 10.6

8. Gwajin Leak tare da Matsi don Masu Canza Liquid Immersed - gwajin yayyo a 15 kPa za a gudanar da shi na sa'o'i 12 ba tare da yabo ba. Babu nakasar dindindin.

9. Ma'aunin Juriya na Insulation

10. Gwajin Dielectric Oil

500 kva utility pad mounted transformer-load losses tests
500 kva utility pad mounted transformer-electrical-test

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

0.171

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Dyn1

0.03% ~ 0.05%

Wuce

3

zango{0}}gwajin dangantaka

/

Dyn1

Dyn1

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

Hakuri don babu asarar kaya shine +0%

0.13%

0.544

Wuce

5

Load hasarar impedance ƙarfin lantarki da inganci

%

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

Haƙuri don impedance shine ± 7.5%

Haƙuri don jimlar asarar kaya shine +0%

Ingancin ba kasa da 99.35%

5.70%

4.453

4.997

99.38%

Wuce

6

Gwajin Karfin Wutar Lantarki

kV

HV: 40kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):

0.960

Duration(s):40

Mitar (HZ): 180

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Gwajin Leaka

kPa

matsa lamba: 15kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

HV{0}LV zuwa Kasa:

LV -HV zuwa Ground:

HV&LV zuwa Ground:

5.11

4.87

5.08

/

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 40

52.3

Wuce

 

 

04 Shiryawa da jigilar kaya

utility pad mounted transformer packing utility pad mounted transformer shipping
 
 

05 Yanar Gizo da Takaitawa

Scotech's 500 kVA guda uku -kushin lokaci{2}}wanda aka ɗora tasfomawanda aka gina shi da iskar tagulla da sanyaya KNAN, injin na'urar tana amfani da man ester na halitta FR3{1}yana inganta lafiyar wuta da rage tasirin muhalli. Madaukinsa{3}}tsarin ciyarwa da matattu-ƙirar gaba yana haɓaka aminci da sassauci don shigarwa da kiyayewa. Tare da rashin ƙarfi na 5.75% da ƙarancin asarar makamashi, yana tabbatar da kwanciyar hankali, ingantaccen aiki a duk yanayin da ake buƙata.

Ana haɗo kowane taswira na Scotech tare da kulawa da ƙasa{0}} don karɓuwa. An ba da fenti mai dacewa da taɓawa{2} sama don kiyaye juriyar lalata da daidaiton gani bayan shigarwa.

Tare da mai da hankali mai ƙarfi akan inganci da aiki{0}aiki, Scotech yana ci gaba da samar da kushin dogaro{1}}wasa na'urorin wuta don tsarin wutar lantarki na zamani a faɗin Arewacin Amurka da bayansa.