Agusta 14, 2026 - SCOTECH ya maraba da abokan ciniki uku daga Nicaragua don gwajin karɓar masana'anta na injin wutar lantarki na SFZ-20000/25000-138 da aka ba da umarnin a baya, tare da rangadin wurin nunin kamfanin da wuraren masana'anta. Babban Manajan SCOTECH, tare da ƙungiyoyin fasaha, samarwa, da ingantattun ƙungiyoyi, sun shirya ziyarar kuma sun ba da kyakkyawar maraba ga baƙi.

Shaida Ƙaƙƙarfan Gwaje-gwaje - Duk Bayanan Ayyukan Aiki sun Wuce Ƙirai
Na'urar da ke ƙarƙashin karɓa tana da ƙididdigan ƙarfin 20 MVA (ONAN) / 25 MVA (ONAF), tare da babban ƙarfin ƙarfin 138 kV da ƙananan ƙarfin ƙarfin 34.5 kV, ƙungiyar vector YNyn 0+d, da kewayon tapping na ± 10 × 1.25%. An ƙera shi kuma an ƙera shi cikin cikakkiyar yarda da ka'idodin IEC 60076. A cikin babban dakin gwajin wutar lantarki na SCOTECH, abokan cinikin sun lura da cikakken tsarin gwaje-gwaje na yau da kullun da nau'in gwaje-gwaje, gami da:

  • Gwajin Ƙunƙarar Walƙiya (LI): An yi amfani da mafi girman ƙarfin lantarki na 650 kV zuwa gefen HV. Ma'aunin ma'aunin igiyar igiyar ruwa sune T{2} μs da T2≈47 μs na dukkan matakai guda uku, duk suna wucewa a farkon yunƙurin ba tare da faɗuwa ko walƙiya ba. Gwajin yankakken-girgiza kuma an yi shi mara aibi.
  • Gwajin Karfin Wutar Lantarki (AV): The gefen LV aka hõre 95 kV zuwa duniya, da kuma HV tsaka tsaki zuwa 140 kV zuwa duniya, duka ga 60 seconds, tare da barga yayyo halin yanzu da kuma abin dogara rufi.
  • Gwajin Ƙarfin Wutar Lantarki tare da Ma'aunin Fitar da Sashe (IVPD): A 1.58Ur/√3 na mintuna 5, matakin sakin juzu'i ya kasance ƙasa da 80 pC a duk faɗin, ya fi tsayi da ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun tsari, yana nuna tsaftataccen tsarin rufewa.
  • Auna Matsayin Sauti: Ma'aunin sautin da aka auna shine 57 dB a ƙarƙashin ONAN da 69 dB a ƙarƙashin ONAF, duka biyun sun fi ingancin garantin Kasa da ko daidai da 80 dB. Abokan ciniki da kansu sun tabbatar da karatun tare da mitar matakin sauti na hannu akan wurin.
  • Asara babu kaya: Auna a 18.262 kW (labbas 22 kW),16.9% mafi kyau fiye da buƙatun kwangila.
  • Load Loss (ONAN): An auna a 69.071 kW (labbas 72 kW),4.1% mafi kyau fiye da ƙimar garanti.
  • Impedance na gajeren lokaci: An auna a 10.5%, daidai daidai da ƙimar ƙira.
  • Juriya na iska na DC, karkatar da rabo, rashin ƙarfi-jeri-sifili, da Ƙwararren Amsa Amsa (FRA) daidaitawa.duk sun hadu ko sun wuce ƙayyadaddun fasaha. Musamman ma, masu lankwasa FRA sun nuna kyakkyawan daidaito na matakai uku, wanda ke nuna babu nakasar iska.

Abokan ciniki sun yi nazari a hankali duk danyen bayanai da oscillograms don kowane gwaji kuma sun nuna babban godiya ga daidaiton kayan gwajin SCOTECH da ƙwarewar ma'aikatan aiki. A ƙarshen tsarin karɓa, abokan ciniki sun sanya hannu kan takardar shaidar karɓar masana'anta a wurin.

be8025b961b65061a3ca2c03e4ce69ed
11b31ebced0b2156a43f04600a7e1d1a
5a0c6472fe04b30472a2d911df16aced
4c8ca429b9208898c76b6aa6b04118be

Zurfin Nunin Nuni da Yawon shakatawa na Masana'antu - Kwarewar Kyawun Masana'antar SCOTECH
Yayin rangadin dakin nunin, abokan ciniki sun sami cikakkiyar fahimtar tarihin SCOTECH a matsayin mai kera taswira ta duniya, ainihin haƙƙin sa na fasaha, da babban fayil ɗin aikin sa na duniya. Abubuwan da aka nuna na yau da kullun sun shafi Arewacin Amurka, Turai, Asiya, Amurka ta Kudu, Afirka, da Oceania, yana ba baƙi cikakken hoto na zurfin kasancewar SCOTECH na duniya.

0549c93fafa46cb9a84a686d0a9c2457
98c0adb2e272ebd19eaa92b666809b8a

Abokan ciniki daga nan sun yi tafiya ta wurin samar da bitar, suna ziyarta a jerecore stacking shop(high-permeability hatsi-daidaitacce silicone karfe yankan, atomatik stacking, da kuma dauri),shagon nadi(nau'in faifan juzu'i na juzu'i, latsawa, da bushewa),rufi sassa machining cibiyar(daidaitaccen yankan kwali da kafawa),taro na ƙarshe da wuri mai cike da mai(core taro, gubar walda, injin bushewa, da mai cika), da kumagama tashar gwajin samfur. Abokan ciniki sun ba da kulawa ta musamman ga ingancin waldawar tanki, tsarin rufewa, da ƙimar kariyar masu sanyaya. Manajan samarwa na SCOTECH ya gabatar da dalla-dalla da na'urorin ƙarfe na bakin karfe, NBR gaskets, tsarin zane mai tsayi na C5M (wanda aka ba da garantin fiye da shekaru 15), da mai ɗaukar hoto tare da matashin mai da na'urar bushewa. Taron bita mai tsafta da tsari mai kyau, kayan aiki mai sarrafa kansa, da tsauraran bayanan binciken aiki - tare da katunan inganci masu zaman kansu don kowane mataki - ya bar tasiri mai ƙarfi akan abokan ciniki.

8870383d7748e849207c976b07a0a46e
1cf113452ef2335044fa795bb34adfc5
e25a1a51ccab1963e2b92a60935ab7b0
0c7a7011ee3924d47ff9141bc317f630
4db2583a39fa3eeb4f20765daec4431c
b17887667ae4bea3c3477bbe4ca9094e

Yabon Abokin ciniki da Haɗin kai mai Alƙawari
Wakilin abokin ciniki yayi sharhi: "Daga sigogin ƙira zuwa tsarin masana'antu, daga bayanan gwaji zuwa gudanarwar rukunin yanar gizon, SCOTECH ya nuna matsayin duniya. Ayyukan wannan na'urar ta atomatik har ma ya wuce tsammaninmu, musamman hasara da alkaluman amo, waɗanda muka gamsu sosai da su.

A mayar da martani, Babban Manajan na SCOTECH ya ce: "Nasarar yarda da naúrar farko ga abokin cinikinmu na Nicaragua shine mafarin amincewa da juna. SCOTECH za ta ci gaba da samar da samfuran abin dogaro da sabis na ƙwararru don tallafawa ci gaban grid na abokin ciniki da haɗin gwiwa inganta canjin makamashi mai tsabta."

An kammala rangadin karɓuwa da shuka cikin nasara, yana ƙara ƙarfafa martabar SCOTECH a kasuwar Amurka ta Tsakiya. SCOTECH ya kasance mai himma ga ka'idodin "inganci, dorewa, da alhakin muhalli," yana ba da ingantattun hanyoyin samar da wutar lantarki ga abokan ciniki a duk duniya.