15 MVA Mataki Up Canjin Wuta-4.16 / 69 kV|Guyana 2023

15 MVA Mataki Up Canjin Wuta-4.16 / 69 kV|Guyana 2023

Kasar: Guyana 2023
Yawan aiki: 15MVA
Wutar lantarki: 4.16/69kV
Feature: tare da OLTC
Aika Aikace-aikacen

 

 

step up power transformer

Ƙarfin ƙarfi mai ƙarfi, yana ƙarfafa gaba{0}zaɓi na'urorin wutar lantarki don haskaka kowane watt na makamashi!

 

01 Gabaɗaya

1.1 Fagen Aikin

Wannan 15 MVA power man immersed transformer mu ne ya kera shi a cikin 2023, ƙimar wutar lantarki 15 MVA, ƙarfin farko shine 4.16 kV tare da +4×1.667% zuwa -12×1.667% tapping range(OLTC), ƙananan ƙarfin lantarki shine 69 kV. Mun samar da wannan OLTC mataki up ikon transformer a cikin kayan tsarin ya dauki jerin manyan canje-canje, tare da haske nauyi, kananan size, kananan partitioning fitarwa, low asara, low amo, high AMINCI, kwatsam short-kewaye singularity kariya, zai iya rage babban adadin ikon grid asarar, aiki halin kaka da kuma tattalin arziki amfanin. Yanayin haɗin YNd11 yana ba da dacewa mai kyau na grid, yayin da yake murkushe masu jituwa na uku da haɓaka ingancin aikin grid yadda ya kamata. Babban bangaren wutar lantarki (Y) haɗin tauraro ne tare da tsaka tsaki wanda za'a iya yin ƙasa kai tsaye ko ta hanyar juriya na ƙasa don samar da ingantaccen ƙarfin lantarki mai ƙarfi.

 

1.2 Ƙayyadaddun Fasaha

100 MVA ikon canza canji da takardar bayanai

Isarwa zuwa
Guyana
Shekara
2023
Samfura
SZ-15 MVA-69kV
Nau'in
Mai Narke Mai Canza Wutar Lantarki
Daidaitawa
IEEE C57.12.00
Ƙarfin Ƙarfi
15 MVA
Yawanci
60HZ
Mataki
Uku
Nau'in Sanyi
ONAN
Babban Voltage
69kV ku
Na biyu Voltage
4.16kV
Abubuwan Iska
Copper
Ƙungiyar Vector
YNd11
Impedance
9.10%
Matsa Canji
OLTC
Taɓa Range
+4*1.667%~-12*1.667%@HV side
Babu Asara Load
10.234KW(20 digiri)
Akan Rasa Load
64.220KW(85 digiri)
Na'urorin haɗi
Daidaitaccen Kanfigareshan
Jawabi
N/A

 

1.3 Zane

15 MVA ikon wutar lantarki zane da girman zane.

step up power transformer diagram step up power transformer nameplate

 

step up power transformer wiring diagram 15mva power transformer drawing

 

 

02 Masana'antu

2.1 Kori

Kamfaninmu yana ɗaukar babban -volt mai ɗaukuwa{1}}sanyi mai karkata{2}}aramin ƙarfe na silikon birgima, babu- rami mai ɗaure, tsarin firam, d{4}tsarin tsarin karkiya don nada maimakon babban dandamali- yanki, mahaɗaɗɗen haɗin gwiwa. Jigon yana da ƙananan burr da ƙananan lamination coefficient. A'a -asarar lodi, babu{9}}allon halin yanzu da matakin amo ana rage su yadda ya kamata ta hanyar mahaɗin mahaɗar ƙarfe na ƙarfe.

core of the transformer

 

2.2 Guda

Continuous winding design

1. Ci gaba da ƙira na iska: Tangle ɗaya ci gaba nau'in da farantin ciki na ci gaba da nau'in ƙira ana amfani da shi, wanda ke taimakawa don haɓaka rarraba ƙarfin tsayi na nada a ƙarƙashin ƙarfin ƙarfin kuzari. Wannan zane zai iya rage ƙaddamar da filayen lantarki, don haka kullun yana da mafi kyawun aikin lantarki a babban matsin lamba.

2. Tsarin zagayawa mai jagora: ana amfani da tsarin zagayawa mai shiryarwa don taimakawa rage haɓakar iska. Wannan zane yana kula da zafin jiki a cikin nada kuma yana taimakawa wajen inganta aminci da kwanciyar hankali na mai canzawa.

 

2.3 Tanko

1. Seling Performance: An rufe tankin mai tare da iyakacin tsayawa don tabbatar da cewa za a iya rufe mai mai da wuta ta yadda ya kamata a cikin tankin mai don guje wa yabo da iskar shaka na mai.

2.Anti{1}maganin lalata: Tankin mai an yi shi ne da abubuwa masu juriya, kuma ana amfani da maganin fenti da ake buƙata don kayan aikin gida don haɓaka juriyar lalata tankin mai da tsawaita rayuwar sabis.

3. Gwajin ganowar leak: walda da hatimin tanki sun yi gwajin gano ɗigo uku (hasken haske, matsi mai kyau, gwajin zubar da jini mara kyau) don tabbatar da ƙarfi da aminci.

oil tank

 

2.4 Taron Karshe

oil conservator

Haɗin ƙarshe na na'ura mai ba da wutar lantarki na mai - wanda wani kamfani ya samar ya ƙunshi matakai da yawa:

1. Core Assembly: Babban taro shine yawanci mataki na farko a tsarin taro na ƙarshe. Wannan ya haɗa da tarawa da danne na'urar wutar lantarki, wanda ya ƙunshi manyan laminations na ƙarfe na ƙarfe na lantarki. Dole ne a haɗa ainihin ainihin ƙayyadaddun bayanai don tabbatar da ingantattun kaddarorin maganadisu da ƙarancin asarar asali.

2. Shigarwar Windings: Tsarin ya haɗa da shigar da manyan iskar wutar lantarki (HV) da ƙananan ƙarancin ƙarfin lantarki (LV) zuwa ainihin. Winding ɗin yawanci keɓaɓɓun madugu na tagulla ne waɗanda aka sanya su a hankali, a jera su, kuma an haɗa su bisa ga ƙirar taswirar.

3. Shigar Tanki da Radiator: Ana shigar da tanki mai canzawa, tare da duk wani radiators mai alaƙa ko sanyaya, a wannan matakin. Tankin yana ba da gidaje don cibiya da iska kuma ana iya rufe shi don ƙunshe da mai.

4. Insulation, Connections, and Accessories: Insulating Tsarin, kamar bushings, lead, famfo, da sauran na'urorin haɗi ana shigar da kuma haɗa zuwa windings. Ana ƙara ƙarin rufi da tallafi don tabbatar da aiki mai aminci da aminci.

5. Cikewar Mai da Rufewa: Ana cika tafsirin mai da mai ta hanyar kulawa da hankali. Da zarar an cika, sai a rufe tafsirin don hana shigar danshi da kuma kiyaye amincin mai.

 

 

03 Gwaji

Gwajin juriya na insulation: ana amfani da shi don gano ingancin kayan aikin don hana rushewar rufin. Wajibi ne a tabbatar da cewa taransfoma ba ta layi ba kuma a yi amfani da kayan gwajin da suka dace.

Gwajin wutar lantarki mai inganci: Ana amfani da wutar lantarki mai girma akan mai canza wuta yayin gwajin don gwada aikin insulate a ƙimar ƙarfin lantarki. Wannan yana buƙatar tsattsauran riko ga amintattun hanyoyin aiki da bada garantin cewa kayan aikin gwaji sun cika ka'idoji.

Gwajin matsi mara kyau: Wannan kayan gwajin yana nazarin aikin insulation na na'ura mai canzawa a ƙaramin wuta. Hakanan wajibi ne a ɗauki matakan tsaro da suka dace don tabbatar da cewa an yi gwajin lafiya.

Gwajin juriya na Ac: Gwada juriya na ƙasa na iska don tabbatar da amincin tsarin ƙasa.

Rashin wutar lantarki kuma babu - ɗora gwaje-gwaje na yanzu: Ana amfani da waɗannan gwaje-gwajen don auna aikin babu{1} da ɗaukar nauyin injin na'ura.

Gwajin lodi: Ta hanyar amfani da nauyin da aka ƙididdigewa, ana auna ma'auni na aikin na'ura mai canzawa a ƙarƙashin ƙimar nauyin kaya.

 

transformer type test

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Marufi da jigilar man tasfoman wutar lantarki da aka nutsar da kamfanin taransfoma ya ƙunshi matakai da yawa don tabbatar da isar da kayan aiki cikin aminci da aminci. A ƙasa akwai cikakken bayanin tsari:

1. Packing: Da zarar na'urar ta wuta ta yi taro na ƙarshe, gami da gwaje-gwaje da bincikar inganci, an shirya shi don ɗaukar kaya. Abubuwan da aka gyara, gami da tanki, core, windings, da na'urorin haɗi, an kiyaye su a hankali da kuma kiyaye su don sufuri. An zaɓi kayan tattarawa, kamar akwatunan katako, kumfa, da ɗauri, don samar da isassun matattakala da kariya.

2. Kiyayewa da Kariyar Lalacewa: Ana kula da abubuwan da aka gyara na taswira tare da ma'auni masu dacewa don kare kariya daga lalata yayin sufuri da ajiya.

power transformer specification

 

4.2 Shipping

15mva power transformer manufacturer

Amintacce don Sufuri: Abubuwan da ake amfani da wutar lantarki ana kiyaye su a cikin marufi don hana motsi da kuma tabbatar da kwanciyar hankali yayin sufuri. Ana kiyaye tsari mai amintacce da daidaito don hana damuwa mara kyau a kowane bangare na taransfoma.

Ganewa da Takardun Takaddun shaida: Kowane ɓangaren fakitin an yi wa lakabin, kuma an shirya cikakkun bayanai, gami da lissafin tattara kaya, umarnin jigilar kaya, da duk wani izini da ake buƙata ko takaddun shaida don sufuri.

Lodawa da Sufuri: Ana ɗora abubuwan da aka ɗora a kan motocin jigilar da suka dace, kamar tireloli masu faɗi ko kwantena na jigilar kaya, ta amfani da cranes ko wasu kayan aiki. Ana iya buƙatar sufuri na musamman don girman ko manyan tasfotoci.

Karɓawa da Saukewa: Lokacin jigilar kayayyaki, ana sarrafa abubuwan da aka haɗa da transfoma da kulawa don hana lalacewa. Bayan isowa wurin da aka nufa, ana kulawa yayin sauke kaya don tabbatar da lafiya da kulawa da kyau

 

 

05 Yanar Gizo da Takaitawa

Shiri: Tabbatar da kafuwar ta kasance lebur kuma barga, kuma duk kayan aikin suna shirye.

Sufuri da Hawan hawa: Kawo da taransfoma zuwa wurin, ɗaga shi zuwa wuri, kuma a tsare shi.

Shigar da haɗe-haɗe: Sanya na'urorin haɗi kamar na'urorin sanyaya, mai adana mai, da bushes.

Haɗin Wutar Lantarki: Cika haɗin haɗin don manyan igiyoyi masu ƙarfi da ƙarancin wuta ko sandunan bas kuma tabbatar da ƙasa mai kyau.

Cika Mai da Dubawa: Cika transfoma da mai mai hana ruwa kuma duba matakan mai da inganci.

Gwaji da Gudanarwa: Yi gwaje-gwajen lantarki kamar surufe, juriya, da gwajin rabo.

Ayyukan gwaji: Gudanar da aikin gwaji a ƙarƙashin kaya kuma tabbatar da duk sigogi kafin ƙaddamar da ƙarshe.