75 kVA Dutsen Dutsen Wuta-14.4 / 0.277 kV|Kanada 2025
Yawan aiki: 75kVA
Wutar lantarki: 24.94GrdY/14.4-0.48/0.277kV
Siffar: tare da kashe{0}}mai canjin kewayawa

Pole Mounted Transformers: Isar da Wuta A Inda Yake Bukata.
01 Gabaɗaya
1.1 Fagen Aikin
An isar da tasfoma guda 75 kVA guda ɗaya na sandar sandar wuta zuwa Kanada a cikin 2025. Ƙarfin da aka ƙididdige ikon na'urar shine 75 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 24.94GrdY / 14.4 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.48 / 0.277 kV, kuma sun kafa ƙungiyar vector na Ii6.
A matsayin mahimmin hanyar haɗi mai haɗa babban grid{0} ƙarfin lantarki don ƙare masu amfani-masu amfani, madaidaicin sandar sandar sandar wutan lantarki tana taka muhimmiyar rawa a cikin samar da wutar lantarki na yau da kullun don mazauna, ƙauye, da ƙanana - yanayin kasuwanci. Ba kamar manya-manyan na'urar taransifoma ba, ana shigar da ita kai tsaye a kan sandunan kayan aiki, yana ba da damar sassauƙan turawa a wuraren da ke da iyakacin sarari{5}}kamar titin zama, hanyoyin karkara, ko kusa da kanana kantuna da gidajen gona. Ta hanyar saukar da ingantaccen wutar lantarki mai ƙarfi{7} zuwa aminci, ƙarancin wutar lantarki mai amfani, yana ba da wutar lantarki na gida, injinan noma, da ƙananan kayan kasuwanci, kai tsaye yana tallafawa rayuwar yau da kullun da ayyukan tattalin arziƙin gida. Tare da fa'idodin kulawa mai sauƙi, ƙaramar ƙarar aiki, da juriya mai ƙarfi ga matsanancin yanayi (misali, ruwan sama, ƙura, da canjin yanayin zafi), wannan na'urar ta atomatik yana tabbatar da ci gaba da samar da wutar lantarki har ma a cikin mahalli masu rikitarwa, yana mai da shi ginshiƙi na amintaccen abin dogaro da rarraba wutar lantarki ga al'ummomin duniya.
1.2 Ƙayyadaddun Fasaha
75 kVA iyakacin duniya saka na'ura mai canzawa nau'in bayani dalla-dalla da takardar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Pole mounted transformer
|
|
Daidaitawa
CSA C2.2-06
|
|
Ƙarfin Ƙarfi
75 kVA
|
|
Yawanci
60HZ
|
|
Mataki
1
|
|
Polarity
Ƙara
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
24.94GrdY/14.4kV
|
|
Na biyu Voltage
0.48/0.277 kV
|
|
Abubuwan Iska
Copper
|
|
Matsala ta kusurwa
Ii6
|
|
Impedance
Yafi ko daidai 1.5%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.165 kW
|
|
Akan Rasa Load
1.05 kW
|
1.3 Zane
75 kVA sandar sandar da aka ɗora zane da girma.
![]() |
![]() |
02 Pole Dutsen Transformers Parts
2.1 LV Bushing - BIL: 30 kV; LV Ground Samar da

An ƙididdige ƙananan bushings na ƙarfin lantarki don 30kV BIL, wanda ya fi isa ga gefen LV na naúrar kVA 75 kuma yana ba da tazara mai daɗi. Ana sanya tanadin ƙasa na LV kusa da shi, yana mai da tsaka-tsakin ƙasa madaidaiciya da yarda. Masu aiki za su iya samun dama gare shi cikin sauƙi yayin shigarwa.
2.2 HV Bushing - BIL: 125 kV
A gefen babban ƙarfin wutar lantarki -, gandun daji sun haɗu da 125kV BIL. Wannan ƙimar daidaitattun matakan rarrabuwar Kanada ne kuma yana ba da taswirar ƙaƙƙarfan kariya daga yunƙurin walƙiya. Abu ne mai sauƙi, amma yana ɗaukar nauyi mai mahimmanci a ainihin yanayin grid.

2.3 Rufe madaurin ƙasa

An sanya madaurin ƙasa a fadin murfin tanki. Ayyukansa shine kiyaye duk sassan ƙarfe a daidai wannan damar, ko da akwai ƙananan motsi ko ayyukan kulawa. Yana da ɗan ƙaramin daki-daki, amma yana tabbatar da murfin kuma tankin ya kasance cikin haɗin lantarki a kowane lokaci.
2.4 Mai Haɗin ƙasa
An ɗora mai haɗin ƙasa kusa da tushe. Yana ba da tabbataccen ma'ana don jagoran ƙasa na tashar, kuma kayan aiki galibi sun fi son wannan shimfidar wuri don shigarwa cikin sauri. Da zarar an haɗa shi, yana taimakawa kiyaye tsayayyen hanyar ƙasa yayin kuskure.

2.5 Ƙunƙarar ɗagawa; Mai canza sheƙa; Valve Taimakon Matsi

Ana liƙa maƙallan ɗagawa a kan tanki kuma an yi girman su yadda ya kamata don nauyin na'urar, don haka sarrafa naúrar da crane yana da sauƙi. Babu -mai sauya tapchanger yana ba da daidaitawa ± 2 × 2.5% akan iskar HV; babu wani abu mai rikitarwa, kawai isasshen sassauci don daidaita wutar lantarki. Har ila yau, bawul ɗin taimako na matsa lamba yana nan a saman tanki. A cikin yanayi mara kyau na matsa lamba, yana buɗewa ta atomatik don kiyaye tanki lafiya.
03 Gwaji
An gudanar da gwajin 75kVA -14.4/0.277kV guda ɗaya na sandar sandar wuta da aka ɗora a kan 2025-04-25 (tsawon yanayi: digiri 23.9, RH: 36%) daidai da CSA C2.2-06(R2022) da CSA-2022(R2022). Gwaje-gwaje na yau da kullun sun haɗa da juriya na iska (HV: 9.747-10.786Ω, LV: 5.875mΩ), gwajin rabo (bangaɗi +0.02~+0.06%, ƙungiyar vector Ii6), polarity (Ƙara), hasara mara nauyi/na yanzu (128.9W a 0100% 148.6W / 0.23% a 105%), nauyi asara / impedance (912W a 85 digiri, impedance 2.21%, yadda ya dace 99.11% Mafi girma fiye da ko daidai da 98.94%), ƙarfin lantarki jure (LV 10kV / 60s, jawo 0.2kHz, ƙarfin lantarki 0.2kV, 3/05s). juriya (max 15.7GΩ), gwajin leak na 20kPa / 12h (babu leka), da gwajin mai (ƙarfin dielectric 53.9kV). Duk sun wuce; Ba za a iya kwafin rahoton ba tare da izinin SCOTECH ba, dole ne a gabatar da ƙin yarda a cikin kwanaki 7, kuma ba shi da inganci ba tare da sa hannun mai gwadawa/mai tabbatarwa/mai yarda ba.
|
A'a. |
Gwajin Abun |
Kammalawa |
|
1 |
Ma'aunin Juriya |
Wuce |
|
2 |
Gwajin Rabo |
Wuce |
|
3 |
Gwajin polarity |
Wuce |
| 4 | A'a -asara da tashin hankali na halin yanzu |
Wuce |
| 5 | Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace |
Wuce |
| 6 | Gwajin Karfin Wutar Lantarki |
Wuce |
| 7 | Jarrabawar Juriya da Wutar Lantarki |
Wuce |
| 8 | Ma'aunin Resistance Insulation |
Wuce |
| 9 | Gwajin Leaka |
Wuce |
| 10 | Gwajin Mai | Wuce |
04 Shiryawa da jigilar kaya
4.1 Shiryawa
Wurin da aka ɗora wutan lantarki guda ɗaya yana kunshe a cikin katako mai ƙarfi. Al'amarin yana da girmansa{1} don dacewa da ma'auni na gidan wuta, yana ba da ingantaccen kariya daga firgita na waje, ƙananan tasiri, da danshi yayin sufuri da ajiya. Yana tabbatar da na'urar taswira ta tsaya tsayin daka har sai an shigar da shafin-.

4.2 Shipping

Domin madaidaicin sandar sandar da aka ɗora wutar lantarki, sufuri yana bin ka'idar CIF tare da EDMONTON azaman tashar jiragen ruwa. Mai siyarwar yana da alhakin yin ajiyar sararin jigilar teku, isar da katako{1}}kas{2}cukushe taswira zuwa tashar jiragen ruwa na EDMONTON, da ɗaukar farashin inshorar kaya da kaya don ɗaukar haɗarin wucewa. Bayan isar na’urar taranfoma a tashar EDMONTON, mai saye ya karbi kayan, yayin da hadarin na’urar ya riga ya wuce ga mai saye a lokacin da ya tashi daga titin jirgin ruwa na lodi.
05 FAQ

01.Menene Juyin Halitta guda -Tsarin Wuta{1}}Mai Taswira da Me Ake Amfani da shi Don?
02.Menene Matsakaicin Matsakaicin Ƙarfin Ƙarfin Guda ɗaya{0}}Ƙaƙwalwar Tsari{1}}Maɗaukakin Taswira?
Wasu masu ba da kayayyaki na iya bayar da girma dabam idan an buƙata, kodayake da zarar ƙimar ta yi girma, masu amfani suna ƙaura zuwa nau'ikan ƙira guda uku{0} ko pad{1} maimakon. Ya fi dacewa a wannan lokacin.
03.Menene Fa'idodi Idan Aka kwatanta Da Mai Canja Wajen Sauyi Uku{0}?
Akwai da yawa, kuma an san su da kyau a aikin rarrabawa:
Gajerun masu ba da wutar lantarki-, wanda ke nufin ƙananan asara.
Ta hanyar sanya taransfoma kusa da kaya, kayan aiki na iya rage raguwar wutar lantarki da inganta aiki a rana{0}}zuwa{1}}aiki.
Tsarin tsari wanda ke buƙatar kusan babu ƙasa.
Babu siminti pad, babu shinge, kuma babu shinge. Sansanin da kansa ya zama tsarin tallafi, wanda ke kiyaye shigarwa mai sauƙi.
Mafi sauƙin shigarwa da kulawa.
Masu fasaha za su iya samun dama da musanya waɗannan raka'a cikin sauri fiye da na ƙarƙashin ƙasa ko na'ura{0} da aka ɗora, wanda ke adana lokaci{1} musamman lokacin dawo da kuskure.
Gabaɗaya, zaɓi ne mai amfani lokacin da nauyin ya kasance matsakaici kuma wurin shigarwa ya kasance mai ƙarfi ko yadu.
04. Wadanne Wuraren Ginawa ko Kulawa yakamata a lura dasu?
Wasu 'yan abubuwa suna da mahimmanci a nan, kuma yayin da babu ɗayansu mai rikitarwa, suna da mahimmanci don dogaro na dogon lokaci{0}.
Yi amfani da sandar sanda tare da isasshen ƙarfi. Dole ne ya goyi bayan na'ura mai canzawa cikin aminci kuma ya tsaya tsayin daka cikin iska da yanayi.
A kiyaye duk tashoshi da masu haɗin kai da tsabta da kuma shiri sosai{0}. Datti, mai, ko rashin haɗin gwiwa na iya haifar da matsala daga baya. Masu gudanarwa kuma suna buƙatar isasshen sassauci don jure yanayin zafi ko girgiza.
Bincika matakin mai, yanayin mai, da bushing akai-akai idan rukunin yana cike da mai-. Duk wata alamar yabo ko lalacewa ya kamata a magance da wuri.
Tabbatar cewa ƙasa tana da ƙarfi. Kyakkyawan, ƙananan -hanyar juriya na ƙasa yana da mahimmanci don aminci.
Yi duban gani na shekara-shekara. Nemo lalata, nakasawa, tabon mai, ko gurɓatar daji.
Gudanar da gwajin mai da tsaftace daji a kowace shekara 2-3, ko fiye akai-akai a cikin matsanancin yanayi kamar yankunan bakin teku ko masana'antu.
Hot Tags: igiya Dutsen transformers, manufacturer, maroki, farashin, farashi
You Might Also Like
75 kVA Pole Type Transformer-34.5 / 0.12 * 0.24 kV|K...
25 kVA Mai Canjin Wuta na Wuta-13.8 / 0.12 * 0.24 kV...
25 kVA Mai Canjawa Hasken Wuta-13.8 / 0.24 kV|Guyana...
Layin Wutar Lantarki na 50 kVA-13.8 / 0.12 * 0.24 kV...
75 kVA Mai Canza Layin Wuta-13.8 / 0.12 * 0.24 kV|Gu...
100 kVA Mai Canza wurin zama-13.8 / 0.12 * 0.24 kV|G...
Aika Aikace-aikacen