225 KVA Single Phase Transformer Pad-4.8 / 0.12 / 0.24 KV|Kanada 2025
Yawan aiki: 225 kVA
Wutar lantarki: 8.32GrdY/4.8-0.12/0.24kV
Siffar: tare da maɓallin Kirk
Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin mafi aminci masana'antun da masu samar da 225 kva guda na'ura mai canzawa pad{7}}4.8/0.12/0.24 kv|kanada 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

Mai ɗorewa, shiru, ingantaccen aiki - kushin lokaci ɗaya mai ɗaure tafsiri da za ku iya amincewa.
01 Gabaɗaya
1.1 Bayanin Aikin
225 kVAPad mai canzawa lokaci gudaAn isar da shi zuwa Ostiraliya a cikin 2025. Ƙarfin ƙimar wutar lantarki guda ɗaya na kushin wutar lantarki shine 225 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 8.32GrdY / 4.8 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.24 / 0.12 kV, sun kafa ƙungiyar vector na Ii6.
Naúrar tana da manufa don samar da kaya mai hawa ɗaya kamar haɓaka gidaje, hasken titi, ƙananan cibiyoyin kasuwanci, da ayyukan wutar lantarki na karkara inda sarari ya iyakance kuma yana da mahimmanci. Wuraren shigarwa na yau da kullun sun haɗa da tsarin mai amfani-mallakarwa ko masu zaman kansu a cikin unguwannin bayan gari, wuraren shakatawa na masana'antu, da wuraren sabunta makamashi (misali, wutar lantarki ta hasken rana). Transformer ya cika daidaiCSA C227.3kumaSaukewa: CSA802.1bugu na baya-bayan nan, wanda ya sa ya dace da kasuwannin Kanada da Arewacin Amurka. Wurin da yake kewaye da shi na waje da tsarin ciyarwar madauki yana ba da damar haɗawa mara kyau cikin da'irar madauki na ƙasa, haɓaka ci gaban sabis.
Mabuɗin Zane-zane
- Babban inganci & ƙarancin hasara– Mafi ƙarancin inganci99.06%; impedance4%(± 7.5%). Babu-asara Kasa da ko daidai da 10% da jimillar asara Kasa da ko daidai da 6% don guje wa hukunci.
- Aiki lafiya– Matattu-gaba, gina abinci madauki tare da ƙari polarity. Ya hada daMaɓallin maɓallin Kirkdon aiwatar da tsarin sauyawa daidai, hana shiga cikin haɗari cikin sassa masu rai da haɓaka amincin aiki sosai.
- Cikakken kariya & sarrafawa- 4-matsayi load break sauya, kashe-circuit famfo canza canji ± 2 × 2.5%, bayoneti fuse, CLF, matsa lamba taimako na'urar, man matakin ma'auni, saman man zafin jiki ma'auni, da kuma injin matsa lamba ma'auni.
- Zane na waje mai dorewa– M karfe tanki gama a Green Munsell 9GY1.5/2.6; ONAN sanyaya, ma'adinai mai, aluminum windings.
1.2 Ƙayyadaddun Fasaha
225 kVA nau'in kushin na'ura mai canzawa guda ɗaya da takaddun bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
CSA C227.3
|
|
Ƙarfin Ƙarfi
225 kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
8.32GrdY/4.8kV
|
|
Na biyu Voltage
0.24 / 0.12 kV
|
|
Abubuwan Iska
Aluminum
|
|
Ƙungiyar Vector
Ii6
|
|
Impedance
4%
|
|
inganci
99.06%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
Kasa da ko daidai da 0.32 kW
|
|
Akan Rasa Load
Kasa da ko daidai da 3.63 kW
|
|
Launi
Musall 9GY1.5/2.6
|
1.3 Zane
225 kVA zanen kushin wutan lantarki guda ɗaya da girman zane.



02 Masana'antu
2.1 Kori

An yi ainihin silin -ƙarfe mai ƙarfi{1}}madaidaicin ƙarfe na silicon, tare da ingantacciyar ƙira don rage ƙanƙara da asara na yanzu. Ƙarƙashin ƙimar ƙarfin lantarki na 105%, ainihin yana kula da ƙarancin juzu'i, yana tabbatar da kyakkyawan aikin motsa jiki.
Babu - asarar lodi: 248 W
Ba a auna - na yanzu: 0.12%
2.2 Guda
Dukansu HV da LV windings nealuminum, cikakken biyan bukatun abokin ciniki. Ƙimar juriya sun daidaita sosai a duk fatuna.
Sakamakon gwaji ya nuna juriya na HV daga0.4058 Ω zuwa 0.4474 Ω, da LV juriya daga0.7248 mΩ zuwa 1.5990 mΩ, mai gaskatãwa barga aiki karkashin rated load.

2.3 Tanko

An gina tanki dagakarfe mai laushikuma ya gama a cikiMunsell 9GY1.5/2.6 korekamar yadda aka ayyana. An ƙera shi don shigarwa na waje, an sanye shi da ma'aunin matakin mai, na'urar taimako na matsa lamba, ma'aunin matsa lamba, da magudanar ruwa / cika bawuloli.
Tankin ya wuce a20 kPa / 12 hours gwajin yabo- babu yabo, babu nakasu na dindindin, yana tabbatar da kyakkyawan hatimi da juriya na yanayi.
2.4 Taron Karshe
An saita kushin taransfomar lokaci ɗaya a matsayin cikakken haɗe-haɗe guda ɗaya{0}}kushin lokaci{1}}wanda aka ɗora naúrar matattu{2}}gaba, madauki{3}}aikin ciyarwa. Dukkanin manyan abubuwan haɗin wutan lantarki{{5} (maɓallai masu ɗaukar nauyi, mai canza famfo, fis) ana ajiye su a cikin tankin da aka rufe tare da shiga tsakani. AKirki Keytsarin yana tabbatar da cewa dole ne a buɗe maɓalli mai ɗaukar nauyi kafin a iya isa ga sashin fuse. Rukunin LV yana da tashoshi 4-rami spade (240/120V) tare da haɗin ƙasa. Na'urorin saka idanu (zazzabin mai, matakin mai, matsa lamba) ana ɗora su a kan wani yanki na tsakiya. Naúrar tana zaune a kan ƙaƙƙarfan tushe na ƙarfe tare da tsayawar filin ajiye motoci don sauƙaƙe shigarwar wurin. Wannan ƙaƙƙarfan ƙira yana haɓaka aminci, yana rage lokacin shigarwa, kuma yana tabbatar da ingantaccen aiki.

03 Tabbatar da Gwaji (Mafi Muhimmanci)
An yi nasarar kammala duk gwaje-gwaje na yau da kullun. Mahimmin sakamako:
|
A'a. |
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
/ |
/ |
/ |
Wuce |
|
2 |
Gwajin Rabo |
/ |
Bambancin rabon wutar lantarki akan babban tapping: ƙasa da ko daidai da ± 0.5% Alamar haɗi: ii6 |
A: +0.07 B: +0.07 |
Wuce |
|
3 |
Gwajin polarity |
/ |
Ƙara |
Ƙara |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% kW |
I0 :: bayar da ma'auni darajar P0: ba da ƙima mai ƙima juriyar rashin hasara shine +0% |
0.12 0.248 |
Wuce |
|
5 |
Load asarar da impedance ƙarfin lantarki |
% kW kW % |
t:85 ku Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +0% |
4.24 3.027 3.275 99.18 |
Wuce |
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 0.88 Duration(s):30 Mitar (HZ): 240 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
LV -HV zuwa Ground |
11.6 |
/ |
|
9 |
Gwajin Leaka |
/ |
Aiwatar da matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
10 |
Gwajin Dielectric Oil |
kV |
Yafi ko daidai da 45 |
59.5 |
Wuce |


04 Shiryawa da jigilar kaya
4.1 Shiryawa
Tiransfomar tana cike da damshi, anti -vibration, da kuma kariyar tsatsa, dace da jigilar ruwa ko ta ƙasa. An gyara tanki amintacce, kuma na'urorin haɗi an cika su daban-daban tare da cikakken jerin abubuwan tattarawa.
4.2 Shipping
Kowane kaya ya ƙunshi:
- Rahoton gwajin Ingilishi
- Takaddun shaida
- Littafin aiki (ciki har da umarnin aiki na hannu)
- Tabbatar da samfurin fenti
- Akwai akanCIFsharuddan, tare da cikakkun takaddun fitarwa.
05 Taƙaitaccen
|
Al'amari |
Matsayi |
|
Daidaita siga |
Cikakken yayi daidai da ƙayyadaddun abokin ciniki (ƙarfin wutar lantarki, iya aiki, impedance, asara, launi, kayan haɗi, da sauransu) |
|
Daidaitaccen yarda |
Ya dace da CSA C227.3, CSA C802.1, CSA C2.2-06 |
|
Amincewa (gwaji) |
Duk gwaje-gwaje na yau da kullun sun wuce - gami da dielectric, insulation, sealing, asara, da gwaje-gwajen impedance |
|
Tabbatar da inganci |
An ƙera shi ƙarƙashin ISO9001: sarrafa albarkatun ƙasa, a cikin{1}} binciken tsari, cikakken ganowa |

Hot Tags: kushin na'ura mai canzawa lokaci guda, masana'anta, mai kaya, farashi, farashi
You Might Also Like
50 kVA Kushin Haɗa Mai Canjawa-24.94 / 0.24 * 0.12 k...
167 kVA Kushin Dutsen Mai Canjawa-24 * 12 / 0.24 kV|...
50 kVA Single Phase Pad Hawan Rarraba Masu Canjin Ra...
25 kVA Kushin Haɗa Mai Canjawa-24*12 / 0.24 kV|Jamai...
100 KVA Mai Canjin Wutar Lantarki-7.2 / 0.12 * 0.24 ...
37.5 KVA Single Phase Padmount Transformer-23.9 / 0....
Aika Aikace-aikacen