2000 KVA Babban Kushin Wutar Lantarki Mai Wutar Lantarki-13.2 / 0.48 KV|Amurka 2025

2000 KVA Babban Kushin Wutar Lantarki Mai Wutar Lantarki-13.2 / 0.48 KV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 2000 kVA
Wutar lantarki: 13.2/0.48kV
Feature: DOE inganci
Aika Aikace-aikacen

Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin masana'antun da suka fi dacewa kuma masu samar da wutar lantarki 2000 kva general pad mounted transformer -13.2/0.48 kv|Amurka 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

 

general electric pad mounted transformer

Ƙarfin da ba ya katsewa, Amintaccen Tsaro. Kunshin -Bambancin Mai Canjawa.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

2000 kVA three phase pad mounted transformer an isar da ita zuwa Amurka a shekarar 2025. Ƙarfin wutar lantarkin shine 2000 kVA tare da sanyaya KNAN. Babban ƙarfin lantarki shine 13.2GrdY / 7.621 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.48Y / 0.277 kV, sun kafa ƙungiyar vector na YNyn0.

An ƙera shi don haɗawa maras sumul cikin tsarin rarraba wutar lantarki na ƙasa, taswirar da aka ɗora taswirar ita ce babban mafita{0}wajen aiki wanda ya yi fice wajen hawan wutar lantarki{1}}ƙasa da kwanciyar hankali. Manne da ka'idojin kiyaye makamashi na DOE, wannan tafsirin an inganta shi don ƙarancin kaya da asara{4}}, yana isar da ingantaccen ƙarfin kuzari wanda ke fassara zuwa babban tanadin farashi akan rayuwar sabis ɗin sa. A cikin tushen ingantaccen aikin sa shine mai na ester na halitta na FR3, wanda ke ba da kyakkyawan yanayin yanayin zafi da iya sarrafa danshi, yana ba da damar injin taswira don ɗaukar nauyin 20% mafi girma idan aka kwatanta da man ma'adinai {{8}cikakkun raka'a yayin da ake kiyaye yanayin yanayin aiki. Don tabbatar da aikin da ba ya yankewa, na'urar ta atomatik sanye take da babban na'urar kama aiki wanda ke karkatar da igiyoyin ruwa da kuma kare abubuwan ciki daga magudanar wutar lantarki. Garkuwan da aka haɗa a tsaye yana haɓaka ƙarfin dielectric, yana hana rushewar rufi da tabbatar da ingantaccen watsa wutar lantarki. Don sauƙi na kulawa da kulawa, an ɗora akwatin ma'auni na sadaukarwa a gefe, yana ba da damar samun sauri ga bayanan aiki. Foda mai rufi (RAL 9003) na waje yana tabbatar da dorewa a kan matsanancin yanayi, gami da matsanancin zafi da zafi.

Ko hidimar cibiyoyin bayanai, wuraren sayayya, ko masana'antu masana'antu, wannan kushin da aka ɗora tasfoma yana ba da daidaito, inganci, kuma amintaccen rarraba wutar lantarki.

 

 

 

1.2 Ƙayyadaddun Fasaha

2000 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
2000 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
13.2GrdY/7.621kV
Na biyu Voltage
0.48Y/0.277 kV
Abubuwan Iska
Aluminum
Ƙungiyar Vector
YNyn0
Impedance
5.75%
inganci
99.51%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.95 kW
Akan Rasa Load
13.15 kW

 

1.3 Zane

2000 kVA kushin da aka ɗora zane da girman hoto.

general electric pad mounted transformer diagram general electric pad mounted transformer nameplate

 

 

02 Masana'antu

2.1 HV

HV Bushing

HV bushing for pad mounted transformers, misalta ta Chardon's 15-LBI200 model, 15kV Class, 200A loadbreak bushing saka cewa zaren kan daidaitaccen bushing rijiyar 200A. Yana da duk{7}}hanyar jan karfe na yanzu, peroxide{10}}warkarwar EPDM, da garkuwar gudanarwa, saduwa da IEEE Standard 386 don cikakkiyar musanyawa da ingantaccen aiki. An ƙirƙira shi don maye gurbin filin ba tare da cire na'urar lantarki daga sabis ba, yana ba da damar kariya, haɗin haɗin da ba za a iya jurewa ba, yana goyan bayan sauyawa da ayyuka kusa da kuskure, kuma yana ba da damar shigar da kayan aiki kyauta ko kayan aiki mai ƙarfi ta hanyar hex broach na ciki.

 

2.2 LV

LV bushing for pad mounted transformers, wanda samfurin BFG -1/2500 ke wakilta, busasshen guduro ne{9}} nau'in bushing ɗin da ya dace da GB/T4109 da IEC60137. Yana da ƙarfin juriya na busasshen AC 10kV, ƙarfin wutar lantarki mai ƙarfin walƙiya 30kV, fiɗa kaɗan ƙasa ko daidai da 10pC a 1.2kV, gajeriyar lokacin zafi na 62.5kA/2s, da nisa mai rarrafe Mai Girma ko daidai da 35mm. An ƙirƙira shi don shigarwa a kwance, yana da farfajiyar da aka ɗora da tin, yana jure wa nauyin cantilever na 200N, yana aiki a cikin -35 digiri zuwa {17} muhallin digiri, ya zo tare da zoben rufewa na 90×70×6, kuma ya dace da ƙayyadaddun ma'auni na buɗe majalisar.

LV Bushing

 

2.3 Bay -O-Fuskar iska

Bay-O-Net Fuse

Bay{0}}O{{1}Fus ɗin net ɗin don na'urorin wuta masu ɗorawa yana samuwa a cikin 23kV (gefen bango/cover-saka) da 38kV (gefen bango{5}}wanda aka ɗora), wanda aka tsara don amfani da taransfoma da aka cika da ruwa na Envirotemp FR3, mai transfoma ko makamancin da aka amince. Yana nuna iya aiki na hotstick, ginin da ya mutu don aminci, da bangon bango na zaɓi{8} ɗorawa Flapper bawul don rage zubewar mai, yana da jan ƙarfe ko azurfa{9}} plated tashoshi (azurfa{10}}ƙirar ma'auni don 38kV) don amintaccen haɗin gwiwa, yana tallafawa ayyukan ɗaukar nauyi, kuma yana ba da izinin dubawa mai sauƙi ba tare da kayan aiki na musamman ba. Dole ne a yi amfani da shi a jeri tare da hanyar keɓewa ko na yanzu{13}}iyakance fuse don hana manyan laifuffuka na yanzu, yana tabbatar da kariya ga taswira da tsarin rarrabawa.

 

2.4 Bawul ɗin Sakin Matsi

An ƙera bawul ɗin sakin matsa lamba don kare tankin mai canzawa daga matsananciyar ciki. Yana buɗewa ta atomatik nan take don sakin iskar gas lokacin da tankin tanki ya kai daidaitaccen ma'aunin sakin psi na psi 10 (wanda ake iya sabawa) kuma yana rufe da zarar matsa lamba ya faɗi zuwa matakin aminci, tare da zaɓin taimako na matsi ta hannu ta hanyar jan hoop ɗin sa. Featuring wani misali 1 / 4-18NPT hawa dunƙule (customizable), shi aiki a cikin mahalli tare da 0 ~ 80 digiri zazzabi da kuma<95% humidity, requires sealant for sealed installation, should be kept away from high-traffic areas to avoid harm from high-temperature released gas, and is not suitable for corrosion-prone sites damaging rubber and copper.

Pressure Release Valve

 

2.5 Ma'aunin zafi da sanyio

Transformer Thermometer

Thermometer BWS-70 mai canzawa don masu canji na pad an ƙera shi don nuna zafin mai a cikin tankin mai canzawa, yana nuna babban hankali, bayyananniyar karatu, tsari mai sauƙi da babban aminci. An yi al'amarinsa da bakin karfe, yana tabbatar da kyan gani da tsawon rayuwar sabis. Don madaidaicin nunin zafin jiki, dole ne a saka kwan fitilar ma'aunin zafi da sanyio fiye da 100mm a cikin matsakaici; ya kamata a kiyaye shi daga karo, lankwasa da nakasawa a lokacin sufuri da amfani, ba za a yi amfani da harsashi na ma'auni a matsayin spanner yayin shigarwa ba, kuma ana buƙatar rajistan shekara-shekara yayin aiki.

 

 

03 Gwaji

Gwaje-gwaje na yau da kullun na 2000kVA guda uku{1}}wani kai{2}mai sanyaya ruwa{3}}mai sanyaya ruwa mai ɗorewa (samfurin: 0.48Y/0.277-13.2GrdY/7.6kV) yana manne da ƙa'idodin IEEE (misali, C21}052). C57.12.34-2022. Duk gwaje-gwajen sun wuce tare da ingantattun sakamako, sun cika sharuddan karɓa ba tare da batutuwa kamar rugujewar wutar lantarki ko zubewa ba.

C57.12.00
C57.12.34

 

 

04 Shiryawa da jigilar kaya

general electric pad mounted transformer packing
shiryawa
general electric pad mounted transformer shipping
jigilar kaya

 

 

 

05 Yanar Gizo da Takaitawa

A SCOTECH, an ƙera taffofin mu masu ɗorawa don sake fayyace dogaro, inganci, da aminci ga tsarin makamashi da ake rarrabawa{0}daga gonakin hasken rana da wuraren ajiyar makamashi zuwa grid na kasuwanci da unguwannin zama. An gina shi da rugujewar yanayi{2}}tsari masu juriya da daidaito{3}}inginen kayan aikin, suna isar da daidaitaccen aiki har ma a cikin mafi tsananin muhallin waje, yana rage raguwar lokaci da rage tsadar aiki na dogon lokaci.

Mun fahimci cewa kowane aiki yana da buƙatun wutar lantarki na musamman. Wannan shine dalilin da ya sa na'urorin da aka ɗora su a cikin pad ɗinmu ana iya daidaita su don saduwa da takamaiman ƙarfin lantarki, iya aiki, da buƙatun haɗin kai, tabbatar da dacewa mara kyau tare da kayan aikin da kuke da su. Tare da goyan bayan ƙwararrun shekarun da suka gabata na SCOTECH na masana'antar taswira, ingantaccen iko, da tallafin duniya, zaku iya amincewa da samfuranmu don ƙarfafa ayyukanku tare da kwanciyar hankali mara nauyi. Haɗin kai tare da SCOTECH don tasfoma masu ɗorewa waɗanda ba kawai sun cika ka'idodin masana'antu ba{3}} sun saita su. Bari mu gina ingantaccen makamashi mai dorewa nan gaba tare.

weather-resistant tank

 

Hot Tags: babban kushin lantarki wanda aka ɗora wutar lantarki, masana'anta, mai kaya, farashi, farashi

Aika Aikace-aikacen