Bayanin Kirk Key Interlock
Dec 09, 2025
Bar sako

Kirk Key interlocks ƙwararrun na'urorin aminci ne na inji waɗanda aka ƙera don rage haɗarin lantarki a cikin tsarin mai canzawa ta hanyoyin aiwatar da aiki na wajibi. Ba kamar makullai na asali ko kariyar lantarki ba, waɗannan “maɓallai masu tarko{1}}” suna amfani da tsarin tarko na maɓalli na zahiri da tsarin sakin don hana damar shiga abubuwan rayuwa mara izini, rashin aiki na canji na bazata, da bala'o'in walƙiya. Suna da mahimmanci don bin ka'idoji kamar NFPA 70E da ka'idodin amincin lantarki na OSHA. Wannan jagorar faɗaɗa tana bincika cikakkun bayanan fasaha, na ainihi{5}} sauye-sauyen aikace-aikacen aikace-aikacen duniya, da mafi kyawun ayyuka masu aiki, tare da takamaiman mai da hankali kan tura tafsiri.
1. Ma'anar Kirk Key Interlocks don Masu Canzawa: Manufar & Ƙirar Ƙira
Makullan Kirk Key sune maɓallai{0}waɗanda ke aiki da shingayen injinan da aka tsara don sarrafa damar shiga kabad ɗin taswira, masu ɗaukar nauyi, da na'ura mai sauyawa. Babban aikin su shine tabbatar da cewa taransfoma ne kawaide -masu kuzarikafin a ba da dama, kuma - an ƙarfafa shi ne kawai bayan an cika duk ka'idojin aminci (misali, rufe majalisar, tabbatar da sauya sheka). Ba kamar makullai na aminci na gabaɗaya ba, suna warware babban gibi: hana kuskuren ɗan adam tatoshewar jikiayyuka marasa aminci (misali, buɗe majalisar taswirar kai tsaye) maimakon dogaro ga bin bin mai amfani kaɗai.
1.1 Mabuɗin Samfura don Masu Canzawa
Layukan samfura na farko guda biyu suna kula da mahalli na canji, kowanne an inganta shi don takamaiman yanayi:
SD Series (Brass Construction)
An ƙirƙira don saituna na cikin gida ko masu sauƙi na waje (misali, masu taswirar padmount masu ɓoye). Gidaje, gidaje na silinda, da filogi/magudanan juzu'i na ciki an yi su ne da tagulla, tare da maɓallan nickel- na azurfa (7{5}} salon tumbler) don juriyar lalata a cikin mahalli marasa ƙarfi. Wannan jeri yana da tasiri mai tsada don daidaitattun aikace-aikace inda ake sarrafa zafin jiki da danshi.
HD Series (Bakin Karfe Gina)
Ƙirƙira don ƙaƙƙarfan waje, matsanancin zafi{0}, ko gurɓataccen mahalli (misali, masu amfani da wutar lantarki a yankunan bakin teku ko wuraren masana'antu). Dukkan abubuwan da suka shafi mahimmanci{4}} gidaje, silinda, filogi, da maɓallai (salon fil ɗin dowel) - bakin karfe ne, yana ba da damar aiki a cikin yanayin zafi har zuwa digiri 700 F (digiri 371) (vs. 250 digiri F/121 digiri na SD Series).

1.2 Mahimman Iyaka don Kulawa
Mahimmanci, keɓewar Kirk Key yana shiga tsakaniba a ƙera su azaman ikon sarrafawa don wuraren da ke da haɗari gabaɗaya(misali, wuraren ajiyar sinadarai kusa da tasfoma). Manufar su kawai ita ce daidaita hanyoyin samun wutar lantarki da canjin wutar lantarki da taswira tare da ka'idojin haɓakawa-.
2. Yadda Kirk Key Interlocks ke Aiki: Transformer{1}}Takamaiman Gudun Aiki
Jigon aikin Kirk Key yana cikinmaɓalli{0}maɓalli, wanda ke haɗa aikin na'urori biyu ko fiye (misali, kayan aiki na sama da na'ura mai canzawa). A ƙasa akwai daki-daki, mataki{3}}ta{4}}arfafa tsarin tafiyar da aiki don na'urar transfoma na yau da kullun:
2.1 Jiha ta Farko (An Karfafa Mai Sauƙi)
- Transformer yana raye, tare da na'ura mai ɗaukar nauyi na sama (LBS) a cikin "rufe" matsayi.
- An shigar da maɓalli na Kirk akan LBS: maɓallin (misali, Maɓalli A-1) shinetarkoa cikin makullin, da bakin kulle kulle bakin karfe (diamita 5/8, daidaitaccen tafiya 3/4){4}} yana kiyaye hannun LBS don hana buɗewar bazata.
- Makulli na Kirk Key na biyu yana ɗora kan ma'ajin taswira: an tsawaita kullinsa, tare da hana ƙofar majalisar buɗewa.
2.2 Mataki na 1: Ƙarfafa - Ƙarfafa Mai Canjawa
- Don samun dama ga taransfoma, mai aiki ya fara buɗe LBS na sama don yanke wuta. Wannan aikin yana daidaita LBS tare da "matsayi mai aminci."
- Mai aiki yana juya maɓallin kama (Maɓalli A-1) a cikin maɓalli na LBS: wannan yana ƙara kulle kulle, wandaa zahiri yana kulle LBS a cikin "buɗe" matsayi(hana sakewa{0}}ƙarfafawa) da fitar da Maɓalli A-1.
2.3 Mataki na 2: Shiga Majalisar Canji
- Ana saka Maɓallin A-1 da aka saki a cikin maɓalli na majalisar taswira. Juya maɓalli yana ja da kullin kullin majalisar, yana barin ƙofar ta buɗe.
- Da zarar ƙofar hukuma ta buɗe, maɓallin (Key A-1) ya zamatarko kumaa cikin makullin majalisar - tabbatar da cewa ba za a iya rufe kofa ba (kuma ba za a iya dawo da maɓalli ba) har sai an kammala gyarawa.
2.4 Mataki na 3: Sake - Ƙarfafa Mai Canjawa
- Bayan gyarawa, ma'aikacin yana rufe gidan wutar lantarki. Wannan yana daidaita majalisar ministocin tare da "matsayi mai aminci," yana sakin Maɓalli A-1.
- Maɓalli A -1 ana mayar da shi zuwa madaidaicin LBS. Juya maɓalli yana ja da kulli na LBS, yana ba da damar rufe LBS{3}}sake kunna wutar lantarki.
2.5 Hali na Musamman: Multi{1}} Silinda HD Series Matsalolin
Don hadaddun tsarin canji (misali, saitin ciyarwar madauki tare da masu sauya sheƙa), HD Series Multi-makullan Silinda na buƙatarduk maɓallan da suka ɓace da za'a saka su juyakafin a iya sakin kowane maɓalli da aka kama. Misali, 3{5}}Silinda HD interlock mai sarrafa maɓalli biyu zai buƙaci Maɓalli 1 (daga Sauyawa A) da Maɓalli 2 (daga Canja B) saka kafin Maɓalli 3 (don samun damar hukuma)- ƙara ƙarin kariya ga tsarin na'urori da yawa.

3. Mahimman Abubuwan Haɓaka & Ƙididdiga na Fasaha (Mai Canjawa{1}}Mayar da hankali)
Kirk Key interlocks don masu taswira sun ƙunshi abubuwan da ba za a iya sasantawa ba guda huɗu, kowanne tare da ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun wutar lantarki da dorewa. A ƙasa akwai cikakken ɓarna, gami da ɓangarorin fasaha waɗanda ke tasiri haɗewar taswira:
|
Bangaren |
Bayanan SD Series |
HD Series Cikakkun bayanai |
Transformer -Takamaiman rawar |
|
Gidaje & Silinda |
Brass (lalata{0}}mai jurewa ga mahalli masu laushi); lebur/fuska{1}}tsarin tsauni. |
304/316 Bakin Karfe (ya hana gishiri, danshi, da zafi mai zafi); salon hawa daya. |
Yana rufe hanyoyin ciki; haɗe zuwa madaidaicin maɓalli/maɓalli ta hanyar 0.4062" (10.32mm) ramukan hawa. |
|
Kulle Bolt |
5/8 "Diamita bakin karfe; kafaffen 3/4" tafiya; tsayin 0"-7" (wanda aka saba dashi). |
Girman ƙulli ɗaya / tafiya; tsawon 0"-7"; mafi girman ƙarfin juriya don amfani mai tsauri. |
A zahiri yana toshe maɓalli/kofofin majalisar; dole ne a daidaita tare da hannun masu canza canji (yawanci 1-1.5" tsinkaya don daidaitattun ɗakunan katako). |
|
Maɓalli |
Nickel -azurfa; 7 -Filin tumbler (tsarin hana zaɓe); hada da kowane Silinda. |
Bakin karfe; dowel fil (tamper{0}}mai jurewa); sayar daban. |
Ƙaddamar da aiki na jeri; Ƙirar 7-pin/dowel suna hana kwafin maɓalli mara izini. |
|
Abubuwan Haɗawa |
Sama -; 2 ramuka (0.4062 "diamita) don 1-4 cylinders. |
Tushen hawa iri ɗaya; Silinda 5+ yana ƙara ƙare - ramukan da aka ɗora (7/8" daga kowane ƙarshen). |
Yana tabbatar da jeri na kulle-kulle tare da kayan aikin wuta (misali, rike LBS, latch ɗin hukuma). Don silinda 5+, jimlar tsawon=9.5" (24.13cm) + 1.5" (38.1mm) akan kowane ƙarin silinda. |
3.1 Mahimman Ƙididdiga na Fasaha
- Yanayin Zazzabi: SD Series (-65 digiri F zuwa +250 digiri F/-54 digiri zuwa+121 digiri ) don na'urorin wuta na cikin gida; HD Series (-65 digiri F zuwa+700 digiri F/-54 digiri zuwa+371 digiri ) na waje/raka'o'in masana'antu.
- Nauyi.
- Hasashen Bolt: Matsakaicin 7 "na duka jerin biyu; zaɓi na gama gari don masu canji: 1" (25.4mm) don kabad na bakin ciki, 1.5" (38.1mm) don daidaitaccen shinge na padmount.
4. Sharuɗɗan Shigarwa: Mataki - ta -Mataki na Masu Canjawa
Shigar da ya dace shine tushen amincin Kirk Key{0}}ƙwararrun ma'aikata kawai, ƙwararrun ma'aikata(tare da horar da amincin lantarki da sanin tsarin tsarin wuta) yakamata suyi wannan aikin. A ƙasa akwai cikakkun bayanai, taswira{1} takamaiman tsarin shigarwa:
4.1 Pre{1}Shirin Shigarwa
(1) Tabbatar dacewa:
- Tabbatar da mai yin taswira/switchgear yana ba da tanadin abubuwan hawa don maɓalli na Kirk Key.
- Bincika cewa jerin kulle-kulle (SD/HD) ya dace da yanayin (misali, HD don na'urorin wuta na waje a yankunan bakin teku).
- Tattara kayan aikin: rawar jiki (don ramukan hawa na al'ada, idan an buƙata), maɓalli mai ƙarfi (don amintattun ƙusoshin 0.4062"), da zanen fasahar interlock.
(2) Mabuɗin Gudanarwa Prep:
- Don Tsarin SD: Cire maɓallai daga kowane silinda (wanda aka haɗa tare da naúrar) kuma yi musu lakabi (misali, "LBS Key A-1," "Maɓallin Majalisar A-1") don guje wa haɗuwa.
- Don Series HD: Tabbatar cewa maɓallan da aka ba da oda daban suna kan -shafi; lalata ƙarin makullin (Kirk ba shi da alhakin haɗarin aminci daga maɓallan da ba a tantance ba).
4.2 Mataki 1: Dutsen Interlocks akan Switchgear (LBS na sama)
- Daidaita Interlock: Sanya interlock don haka kullin kulle, lokacin da aka tsawaita, zai toshe hannun LBS a jiki daga motsawa zuwa "rufe." Alama wuraren hawan ramin ta amfani da samfurin kulle.
- Tabbatar da Interlock: Drill 0.4062" (10.32mm) ramuka (idan babu pre - tanadin hakowa ya wanzu) kuma a ɗaure tsakar gida tare da lalata{3} ƙuƙumma masu juriya (juyawa zuwa 15–20 ft{6}}lbs don tagulla/karfe).
- Gwada Tafiya ta Bolt: Da hannu mikawa/janye kullin don tabbatar da cewa ya yi daidai da hannun LBS{0}}kada a sami gibi (dole ne a tuntuɓi abin hannu idan an tsawaita) .
4.3 Mataki 2: Dutsen Interlocks akan Majalisar Canji
- Matsayi don Tsaro: Hana interlock akan ƙofar majalisar ko firam don haka kullin, idan an faɗaɗa shi, ya toshe ƙofar daga buɗewa. Tabbatar da kullin ya daidaita tare da tsayayyen ɓangaren majalisar (misali, farantin latch) don guje wa lankwasawa.
- Amintacce kuma Gwaji: A ɗaure tsakar gida kamar yadda yake a Mataki na 1. Rufe majalisar kuma ƙara ƙarar - tabbatar da cewa ba za a iya buɗe ƙofar ba; janye kullin kuma tabbatar da buɗe kofa kyauta.
4.4 Mataki na 3: Tsarin -Gwajin Jeri na Mataki
Wannan shine mafi mahimmancin mataki{0}} gwada cikakken aikin don tabbatar da babu tabo mai aminci:
- Ƙarfafa wutar lantarki kuma tabbatar da kullin LBS yana kama maɓalli, kuma kullin majalisar ya toshe ƙofar.
- De{0}}ƙarfafa LBS, kunna maɓalli don saki shi, kuma yi amfani da shi don buɗe majalisar (maɓalli ya kamata ya kama tarko a cikin maɓalli).
- Rufe majalisar, dawo da maɓalli, kuma amfani da shi don sake ƙarfafa LBS.
- Don maɓallan Silinda da yawa: Gwada tare da duk maɓallan da ake buƙata don tabbatar da cewa ba a saki maɓalli ba har sai an saka duka.
4.5 Kuskuren Shigarwa gama gari don Gujewa
- Bolt mara kuskure: Kullun da ba ya tuntuɓar madaidaicin madaidaicin/makullin majalisar zai iya kasa toshe ayyuka marasa aminci{0}}amfani da shims idan an buƙata don daidaita jeri.
- Sama da -Tsarin Ƙarfafawa: Sama da -Tighting na iya karkatar da gidajen SD Series na tagulla{1}} manne da kewayon juzu'i na 15-20 ft{4}}lb.
- Yin watsi da Lakabin Maɓalli: Maɓallai marasa lakabi suna haifar da kurakuran jeri (misali, yin amfani da maɓalli mara kyau don majalisar ministoci){2}} yi amfani da tambarin dindindin.
5. Kulawa Mafi Kyawun Ayyuka: Tabbatar da Dogarorin Dogarorin Zamani
Makullin Kirk Key yana buƙatar kulawa kaɗan amma ya dogara da kulawa na yau da kullun don guje wa cunkoso ko gazawa{0}mahimmanci don amincin taswira. A ƙasa akwai jadawali da matakan aiki:
5.1 Jadawalin Kulawa (Mai Sauya -Takamaiman)
|
Aikin Kulawa |
Yawanci |
Bayanan kula na Series SD |
Bayanan Bayani na HD Series (Waje/Masana'antu) |
|
Duban gani |
Mako-mako (lokacin duban taranfoma) |
Bincika lalatar tagulla, ƙulle-ƙulle, ko lalacewar maɓalli. |
Bincika tsatsa ta bakin karfe, tarkace a cikin silinda, ko lankwasa. |
|
Dry Graphite Lubrication |
Kowane watanni 6 (na cikin gida); watanni 3 (waje) |
Lubricate key da silinda. |
Lubricate shaft juyi na ciki (bayan silinda). |
|
Binciken Rufin Kariya |
kowane wata |
Na zaɓi (na cikin gida); duba fashe idan aka yi amfani da su. |
Wajibi; duba shiga ruwa ko lalacewa. |
|
Cikakken Gwajin Jeri |
kowace shekara (lokacin kula da transfoma) |
Gwada tarko/saki da tafiye-tafiyen kulle. |
Daidai da SD; ƙara duban lalata don kusoshi. |
5.2 Cikakken Umarnin Lubrication
Me yasa Graphite?: Kada a taɓa amfani da mai ko maiko -wadannan suna jawo ƙazanta da ƙura, waɗanda ke matse silinda akan lokaci. Dry foda graphite (Kirk's GL-1 Kit) yana gudanar da aiki kuma ba zai lalata sassa na inji ba.
SD Series Lubrication:
- Aiwatar da ƙaramin adadin graphite zuwa maɓalli (gram 1-2, isa don ɗaukar saman).
- Saka maɓalli a cikin Silinda kuma yi aiki a ciki/fita sau 5-6.
- Juya maɓalli kusa da agogon agogo 3-4 don rarraba graphite a cikin silinda.
HD Series Lubrication:
- Cire maɓallin kuma gano wurin jujjuyawar ciki (a bayan silinda).
- Aiwatar da graphite kai tsaye zuwa ga shaft (amfani da ƙaramin goga don isa wurare masu tsauri).
- Saka maɓallin kuma juya shi sau 4-5 don yada zane.
5.3 Rufin Kariya: Garkuwar Matsalolin Waje
Don masu kulle-kulle na HD Series akan masu canza wuta na waje, yi amfani da murfin kariya na zaɓi na Kirk:
- Tura{0}Akan Rubutun (Sashe na C): Don ƙananan - wuraren zirga-zirga; matsa kan silinda don hana shigar tarkace.
- Juya -Buɗe Rufe (Sashe na F): Don manyan wuraren zirga-zirgar ababen hawa (misali, taswirar da ake samu akai-akai); sun haɗa da tanadin LOTO (Lockout{3}}Tagout) don kiyaye murfin yayin kiyayewa.
5.4 Matsalar gama gari
|
Alama |
Dalili |
Magani |
|
Maɓalli ba zai juya cikin silinda ba |
Datti / tarkace gini |
Lubricate tare da graphite; busa matsewar iska a cikin silinda. |
|
Bolt ba zai ja da baya ba |
Lanƙwasa kusoshi ko tsaka-tsaki mara kyau |
Duba kullin don lankwasawa; gyara interlock idan an buƙata. |
|
Mabuɗin tarko da wuri |
Ba a cikin "matsayi mai aminci" |
Bincika jeri na makullin tare da na'urar (misali, majalisar ba ta cika rufe ba). |
6. Mai Canjawa{1}}Takamaiman Aikace-aikace: Na Gaskiya{2}} Abubuwan Amfani na Duniya
Kirk Key interlocks suna da nau'ikan tafsiri iri-iri -daga raka'o'in padmount na zama zuwa na'urorin wutar lantarki na masana'antu. A ƙasa akwai aikace-aikace na yau da kullun, tare da cikakkun hanyoyin aiki:
6.1 Aikace-aikacen 1: Padmount Transformer Cabinets (Mai zama / Kasuwanci)
- Manufar: Hana ma'aikata marasa izini (misali, ma'aikatan amfani, ƴan kwangila) buɗe akwatunan kai tsaye.
- Saita: Maɓalli ɗaya a kan maɓallin kayan aiki na sama (misali, maɓalli mai ɗaukar nauyi 12kV) da ɗaya a kan majalisar.
- Gudun aiki: Kamar yadda aka bayyana a Sashe na 2-kawai bayan an buɗe maɓallin mai amfani (kuma an saki maɓalli) za'a iya isa ga majalisar ministocin. Wannan yana da mahimmanci don rage haɗarin walƙiya na baka yayin duban mita ko ƙaramar kulawa.


6.2 Aikace-aikace 2: Load Break Switches (Masu Canjin Masana'antu)
Manufar: Hana aikin layi daya na na'urori biyu na caji (LBS) a cikin da'ira ta biyu (wanda ke haifar da gajeriyar kewayawa).
Saita: Makullin HD Series guda biyu (ɗaya akan kowane LBS) waɗanda aka haɗa ta hanyar maɓallin raba.
Gudun aiki:
- Lokacin da aka rufe LBS A, maɓalli yana cikin tarko a cikin makullinsa{0}}An tsawaita kullin maɓalli na LBS B, yana toshe shi daga rufewa.
- Don rufe LBS B, mai aiki yana buɗe LBS A, ya dawo da maɓalli, kuma yayi amfani da shi don ja da kullin LBS B{0}}yana kama maɓalli a cikin maɓallan LBS B (toshe LBS A daga sake{1}}rufewa).



6.3 Aikace-aikacen 3: Tsarin Ciyarwar Madauki (Masu Canjin Amfani)
Manufar: Tabbatar da ciyarwa ɗaya kawai (A ko B) ke aiki a cikin tsarin ciyarwar madauki (yana hana yin lodin na'urar wuta).
Saita: A 3-Silinda HD Series interlock sarrafa Feed A, Feed B, da gidan wuta.
Gudun aiki:
- Don kunna Ciyar A, mai aiki yana saka maɓallai don Ciyarwar B (dole ne a buɗe) kuma majalisar (dole ne a rufe) cikin maɓalli{0}}yana sakin maɓallin Ciyarwar A.
- Ciyarwar Rufe A tarko ta key; don canjawa zuwa Ciyarwar B, mai aiki yana buɗe Feed A, ya dawo da maɓallinsa, ya saka shi (tare da maɓallin maɓalli) don sakin maɓallin Ciyar B.
7.Jagorar Zaɓa: Zaɓin Maɓallin Maɓallin Kirk ɗin Dama don Mai Canjin ku
Zaɓin madaidaicin madaidaicin yana buƙatar daidaita ƙayyadaddun bayanai tare da mahalli, girman, da buƙatun aikin ku. A ƙasa akwai mataki - ta -Tsarin zaɓi na mataki:
7.1 Mataki 1: Ƙayyade jerin (SD vs. HD)
Yi amfani da wannan lissafin don yanke shawara:
|
Factor |
Zaɓi Jerin SD |
Zaɓi Tsarin HD |
|
Muhalli |
Na cikin gida/gidan waje (ba ruwan sama/gishiri kai tsaye) |
Waje / bakin teku / masana'antu (ruwan sama, gishiri, zafi mai zafi) |
|
Matsanancin Zazzabi |
<250°F (121°C) |
>250 digiri F (121 digiri) har zuwa 700 digiri F (371 digiri) |
|
Hadarin lalata |
Ƙananan (bushe, iska mai tsabta) |
High (danshi, gishiri, sunadarai) |
7.2 Mataki 2: Zaɓi Tsawon Bolt
Tsawon Bolt ya dogara da tazara tsakanin maƙarƙashiya da madaidaicin maɓalli/latch ɗin majalisar. Auna wannan tazarar (kira shi "G") kuma ƙara 1/8" don tabbatar da cikakkiyar lamba. Tsawon gama gari don masu canza wuta:
1" (25.4mm): Bakin ciki na cikin kabad.
1.5" (38.1mm): Daidaitaccen katakon wutan lantarki.
2 ″ (50.8mm): Canjin canjin masana'antu tare da kauri mai kauri.
7.3 Mataki na 3: Zaɓi Yawan Silinda
- 1 Silinda: Saituna masu sauƙi (1 canza {1} majalisa).
- 2-4 Silinda: Masu canjin masana'antu tare da masu sauyawa guda biyu (misali, LBS na farko da sakandare).
- {0} Silinda: Madaidaicin tsarin ciyarwa ko taswira tare da wuraren aminci da yawa (amfani da tsayin dabara: 9.5" + 1.5" kowane ƙarin silinda) .
7.4 Mataki na 4: Ƙara Sauyawa Masu Taimako (Idan Ana Bukata)
Don masu canji da ke buƙatar sa ido na nesa (misali, tsarin sarrafa masana'antu), ƙara maɓallai masu taimako:
- Jerin SDZaɓuɓɓuka sun haɗa da 2 N/O 1 N/C (Sashe A) ko 4 N/O 2 N/C (Sashe na B).
- HD Series: Daidaitaccen zaɓi shine 1 N / O (Sashe na E); daidaitawar al'ada na buƙatar tuntuɓar ƙungiyar tallace-tallace ta Kirk.
7.5 Mataki na 5: Tabbatar da Biyayya & Takaddun shaida
Tabbatar cewa kullin ya dace da ƙa'idodin gida:
- UL Jerin (na Arewacin Amurka) ko CSA Certified (na Kanada).
- Mai yarda da NFPA 70E (Arc flash safe).
- IEC 62271-205 mai yarda (don turawa na duniya).
8. Me yasa Kirk Key Interlocks ba su da mahimmanci don Tsaron Transformer
Masu canza canji suna da yawa - kadarorin haɗari - al'amuran da suka faru na arc na iya haifar da mummunan rauni ko mutuwa, kuma lalacewar kayan aiki na iya haifar da kashe kuɗi mai tsada. Maɓallin Kirk Key yana magance waɗannan haɗari ta hanyoyin da babu wata na'urar aminci da za ta iya:
8.1 Yana Aiwatar da "Ba Ketare" Tsaro
Ba kamar makullai na lantarki (waɗanda za su iya kasawa yayin katsewar wutar lantarki) ko makullai (waɗanda za a iya yankewa ko a yi watsi da su), Makullin Kirk Key sun dogara da aikin injiniya na zahiri{0}}babu wata hanya ta ƙetare jerin. Misali, za a iya cire makullin makullai a kan ma'ajin tasfoma tare da masu yankan bolt, amma kullin maɓalli na Kirk yana buƙatar musanya na sama don a fara samun kuzari da farko .
8.2 Yana Rage Kuskuren Dan Adam
NFPA 70E ta ba da rahoton cewa kashi 70% na al'amuran lantarki sun samo asali ne daga kuskuren ɗan adam (misali, buɗe majalisar ministocin rayuwa). Maɓallin Kirk yana kawar da wannan ta yin ayyuka marasa amincijiki ba zai yiwu ba-Ba za a iya dawo da maɓalli ba, kuma ba za a iya janye kullin ba, har sai tsarin yana da aminci.
8.3 Kudin -Tsarin Doguwa{2}}Wa'adi
Yayin da farashin farko ya fi na makullai, Makullin Kirk Key yana rage kashe dogon lokaci{0}:
Karancin haɗari{0}}kudaden da ke da alaƙa (kuɗin likitanci, tara, ƙararraki).
Kadan lokacin ragewar tafsiri (babu lalacewa daga rashin aiki).
Karamin kulawa (mai mai graphite yana da arha -farashi da maye gurbin makullan lantarki da suka gaza).