315 kVA Vpi Dry Type Transformer-11 / 0.55 kV|Afirka ta Kudu 2025

315 kVA Vpi Dry Type Transformer-11 / 0.55 kV|Afirka ta Kudu 2025

Ƙasa: Afirka ta Kudu 2025
Yawan aiki: 315kVA
Wutar lantarki: 10/0.55kV
Siffar: tare da magoya baya da matakin rufewar H
Aika Aikace-aikacen

 

 

Vpi Dry Type Transformer

VPI Dry{0}Nau'in Masu Canzawa: Mafi Aminci, Ƙarfin dogaro.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

The 315 kVA bude winding busassun irin transformer da aka isar zuwa Afirka ta Kudu a cikin 2025. The rated ikon bude winding busassun irin transformer ne 315 kVA tare da AN / AF sanyaya, na farko irin ƙarfin lantarki ne 11 kV da ± 2 * 2.5% tapping kewayon (NLTC), da sakandare ƙarfin lantarki ne 0.55kV, sun kafa wani vector kungiyar Dyn1.

Wannan samfurin buɗaɗɗen nau'in nau'in tafofi ne-, busasshen Class H{1}} wanda aka ƙera tare da ci-gaba da fasahar Vacuum Pressure Impregnation (VPI), wanda aka kera musamman don buƙatun muhallin masana'antu. Its windings yana sha da yawa VPI jiyya don samar da wani m Class H rufi Layer, samar da na musamman juriya ga danshi, kura, da lalata. An ƙirƙira shi da kayan rufin Class H da haɓakar zafin jiki na 100K, yana ba da ragi mai ƙoshin zafi, yana tabbatar da tsawaita rayuwar sabis da mafi girman ƙarfin lodi ko da ƙarƙashin yanayin zafi mai girma-. Salo na musamman na buɗe-, haɗe tare da ingantattun magoya baya sanyaya, yana ba da damar zafin jiki ta atomatik{8} sarrafa sanyaya iska mai ƙarfi, yana haɓaka ƙarfin ɗan gajeren lokaci-ƙara da ba da damar ingantaccen aiki ƙarƙashin tasirin tasiri. Yana da ƙirar mai kyauta, harshen wuta{12}} ƙira, yana ba da mafi girman aminci da aminci, an inganta shi don tsarin wutar lantarki 110V, kuma ana amfani dashi sosai a masana'antar masana'antu, cibiyoyin bayanai, jigilar jirgin ƙasa, da sauran aikace-aikacen da ke buƙatar babban aminci da aminci a rarraba wutar lantarki.

 

 

1.2 Ƙayyadaddun Fasaha

315 kVA VPI busassun nau'in canji da takaddun bayanai

Isarwa zuwa
Afirka ta Kudu
Shekara
2025
Nau'in
Buɗe busasshiyar taswira
Babban abu
Silicon karfe takardar hatsi daidaitacce
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
315 kVA
Yawanci
50HZ
Ƙungiyar Vector
Domin 11
Mataki
3
Nau'in Sanyi
ONAN/ONAF
Babban Voltage
11 kv
Na biyu Voltage
0.55 kV
Abubuwan Iska
Aluminum
Impedance
4%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2*2.5%@gefen farko ta hanyar latsa hanyoyin haɗi
Babu Asara Load
1.1KW
Akan Rasa Load
4.1KW
Matsayin rufi
H
Haɓakar zafin jiki @ƙimar sabis
100K

 

1.3 Zane

315 kVA VPI busassun nau'in mai canzawa zane zane da girman.

Vpi Dry Type Transformer diagram Vpi Dry Type Transformer nameplate

 

 

02 Masana'antu

2.1 Kori

An gina ainihin maɗaukakin ne daga siliki mai ƙima mai inganci{0} hatsi{1}. Wannan kayan na musamman an lullube shi da rauni don rage ainihin asara da haɓaka ƙarfin maganadisu. Tsarin hatsin sa -yana da mahimmanci yana rage yawan ƙwanƙwasa da asara a halin yanzu, yana tabbatar da ingantacciyar ƙarfin maganadisu da ƙarancin ƙarancin amfani da wutar lantarki-. Madaidaicin aikin injiniya na ainihin yana ba da gudummawa ga ingantaccen aikin na'ura mai canzawa, ƙarancin aikin hayaniya, da kuzarin gabaɗayan ceton aiki-.

 

2.2 Guda

The coils suna amfani da tsaftataccen madubin aluminium mai girma{0}, vacuum -matsi impregnated (VPI) tare da babban{2}} varnish mai hana ruwa. Wannan tsari yana haifar da tsayayyen tsarin danshi - tsarin rufewa mai jurewa wanda ke tabbatar da ingantaccen yanayin zafi, ƙarfin injina, da ingantaccen aiki a ƙarƙashin yanayi mai buƙata.

aluminum conductors

 

2.3 taro na ƙarshe

Electrical connections

Haɗin ƙarshe na busasshen VPI{0}nau'in na'ura mai canzawa yana haɗa cibiya mai ciki da coils zuwa ingantacciyar tsarin injina, mai tsaro tare da firgita mai juriya{1}. Haɗin wutar lantarki daidaici -An ƙare tare da manyan masu haɗa ƙarfi-, yayin da ake shigar da magoya baya masu sanyaya da garkuwa don tabbatar da ingantacciyar sarrafa zafi da amincin aiki.

 

 

03 Gwaji

Gwajin bushewar nau'in taswirar VPI (315kVA-11/0.55kV) akan 2024/12/5, kowane ma'aunin IEC, juriyar juriya da aka rufe (rashin daidaituwa), rabo / lokaci (kananan karkata, Dyn11), gajeriyar - kewayawa/no-lodawa, sigogin ƙarfin lantarki da juriya ga juriya fiye da 1 (babu rushewar ƙasa). Duk sakamakon ya cika buƙatu, masu cancanta.

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

0.37%

0.58%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dyn11

0.02% ~ 0.18%

Domin 11

Wuce

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 120 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

4.27%

2.390

3.329

Wuce

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

0.81

0.9198

Wuce

100% Ur

0.90

1.022

110% Ur

0.99

1.124

5

Gwajin Karfin Wutar Lantarki

/

HV: 35kV 60s

LV: 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Ƙarfin wutar lantarki (KV): 1.1

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

test of VPI dry type transformer
IEC standards test

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

VPI bushe{0}}nau'in tafofi yana kunshe cikin tsaro ta hanyar amfani da yanayi{1}}mai jurewa da girgiza{2}}kayan sha. An ɗora tasfofi da ƙarfi a cikin kwalin katako na al'ada, tare da ƙarin fakitin kariya don hana motsi yayin tafiya. An rufe mahimman abubuwan haɗin gwiwa tare da shingen tabbatar da danshi{5}, kuma gabaɗayan fakitin an yi masa lakabi da ƙayyadaddun umarni da ƙayyadaddun fasaha don tabbatar da aminci da ingantaccen dabaru.

 

4.2 Shipping

Karkashin sharuɗɗan CIF (Cost, Insurance, and Freight), za a aika da busasshen na'ura na VPI{0}} zuwa tashar jiragen ruwa na Durban, Afirka ta Kudu. Mai sayarwa yana ɗaukar jigilar jigilar ruwa da inshorar ruwa, yana tabbatar da kariya ta hanyar wucewa cikin yanayi{2}}mai juriya, marufi{3}marufi. Dukkan takaddun jigilar kaya (lissafin jigilar kaya, takardar shaidar inshora, daftarin kasuwanci) ana tanadar don ingantaccen izinin kwastam a inda aka nufa. Canja wurin haɗari ga mai siye yayin sauke kaya a tashar jiragen ruwa na Durban.

 

 

05 Yanar Gizo da Takaitawa

Nau'in tafsirin VPI bushe{0}} yana tsaye a matsayin ginshiƙin tsarin wutar lantarki na zamani, yana haɗa amincin mara misaltuwa tare da yanke{1}} injiniyan baki. Ta hanyar fasahar Vacuum Pressure Impregnation (VPI), rufin Class H, da sarrafa zafin jiki mai hankali, yana ba da ingantacciyar inganci, harshen wuta{3}}, da ingantaccen aiki a mafi yawan wurare masu buƙata. Daga rarraba wutar lantarki na masana'antu da haɗin gwiwar makamashi mai sabuntawa zuwa mahimman aikace-aikacen ababen more rayuwa, VPI bushe{5}}nau'in taswira yana aiki tare da juriya na shiru, yana tabbatar da isar da wutar lantarki mai tsabta da kwanciyar hankali a duk duniya. Zaɓin wannan transfoma yana nufin saka hannun jari don dorewar tsaro na makamashi da ingantaccen aiki na gaba.

 

Hot Tags: vpi busassun irin na'ura mai canzawa, masana'anta, mai kaya, farashi, farashi