750 KVA Mai Rarraba Rarraba Mataki Uku-11 / 0.415 KV|Papua New Guinea
Yawan aiki: 750 kVA
Wutar lantarki: 11/0.415kV
Feature: Tare da iskar gas
Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin mafi amintattun masana'antun da masu samar da na'ura mai rarrabawa 750 kva uku{5}}11/0.415 kv|papua new Guinea in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

Rarrashin hasara, tsawon rayuwar sabis - Man mai{1}} na'urar rarraba wutar lantarki tana sa rarraba wutar lantarki ta fi tattalin arziki da tsaro.
01 Gabaɗaya
1.1 Bayanin Aikin
Maɓalli Maɓalli & Yanayin aikace-aikace
Ingantacciyar Ƙarfin & Ƙimar Wutar Lantarki– Tare da rated iya aiki na 750kVA, wannanuku lokaci rarraba transformerya dace da rarraba wutar lantarki na masana'anta, samar da wutar lantarki na jama'a, ko manyan wuraren samun wutar lantarki don manyan wuraren kasuwanci. Yana sauka daidai 11kV babban ƙarfin lantarki zuwa 0.415kV ({3}}lokaci huɗu -waya) akan ƙananan ƙarfin ƙarfin lantarki, yana ba da ƙarfin ƙarfi ga yanayin aikace-aikacen daban-daban.
Tsayayyen Ayyukan Lantarki- Samfurin yana ɗaukar aDomin 11kungiyar vector. Wannan hanyar haɗin yanar gizon tana da ƙarfi mai ƙarfi don jure kaya marasa daidaituwa kuma yadda ya kamata yana danne gurɓacewar jituwa ta uku a cikin manyan hanyoyin sadarwa, yana mai da ita dacewa musamman ga wuraren zama da ofisoshi tare da manyan kaya guda ɗaya{1}. Tare da asarar nauyi na 10.3kW a digiri 75 da asarar babu-nauyi na 1.1kW kawai, injin na'ura yana tabbatar da ƙarancin amfani da makamashi yayin tsawaita jiran aiki ko haske -aikin lodi.
Dogarar Ingantacciyar Wutar Lantarki– An sanye da taransfoman da babu{0}}mai canza matsa lamba (NLTC). Lokacin da aka rage kuzari, masu amfani za su iya daidaita ƙarfin lantarki da hannu a cikin kewayon ± 2 × 2.5% don rama faɗuwar wutar lantarki ta hanyar dogon layin watsawa. Idan aka kwatanta da hadaddun akan -masu sauya famfo (OLTC), wannan ƙira ba wai tana rage farashin masana'anta ba ne kawai amma tana kawar da buƙatar haɗaɗɗun abubuwan taimakon lantarki, inganta tattalin arziki da dorewa.
Babban Gudanarwar Thermal & Tsarin Tanki
Transformer na amfani da ONAN (Oil Natural Air Natural) sanyaya. Ya dogara ne da jujjuyawar yanayi na mai na transfoma - mai zafi yana tashi da kuma nutsewar mai mai sanyi - kuma yana watsar da zafi ta hanyar ɓangarorin ƙugiya ko radiators ba tare da fanfo ko famfun mai ba. Wannan ƙira yana inganta ingantaccen kulawa{2}}aiki kyauta da aminci a ƙarƙashin matsanancin yanayin muhalli. Bugu da kari, na'urar transfomer tana da fasalin acikakken man fetur{0}cikakken gini. Tankin da za a iya faɗaɗawa yadda ya kamata ya keɓance iska da danshi na waje, yana faɗaɗa rayuwar mai da ke rufewa da kuma yanayin sake fasalin na'urar.
Gine-ginen Waje Mai Karya & Kariya
An ƙera wannan na'ura mai ɗaukar hoto don matsananciyar muhallin waje, mai ikon yin aiki mai tsayi na dogon lokaci a tsayi har zuwa mita 1000 da yanayin zafi daga - digiri 25 zuwa digiri 40. Dukansu HV da LV bushings an yi su ne daga waje{6}}alin atan, tare da zaɓin akwatunan kebul ɗin da aka keɓance iska don tabbatar da amintaccen kariya ta tasha da isasshiyar sharewa. Cikakken saitin na'urorin haɗi - gami da ma'aunin matakin mai multifunctional tare da taimako na matsa lamba, mai nuna zafin mai, relay Buchholz, da amintattun tashoshi na ƙasa - suna samar da tsarin kariya mai yawa Layer, samar da ƙararrawa na lokaci ko matsa lamba a cikin yanayin kuskuren ciki.
1.2 Ƙayyadaddun Fasaha
750 kVA uku lokaci rarraba tasfo bayani dalla-dalla irin da kuma bayanai takardar
|
Isarwa zuwa
Papua New Guinea
|
|
Shekara
2025
|
|
Nau'in
mai - na'urar rarraba wutar lantarki
|
|
Daidaitawa
IEC 60076-1: 2011
|
|
Tsayi
Kasa da ko daidai da 1000m
|
|
Ƙarfin Ƙarfi
750 kVA
|
|
Yawanci
50HZ
|
|
Mataki
3
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
11 kv
|
|
Na biyu Voltage
0.415 kV
|
|
Abubuwan Iska
Aluminum
|
|
Ƙungiyar Vector
Domin 11
|
|
Matsakaicin hawan mai / iska mai ƙarfi
60 digiri / 65 digiri
|
|
Mai Transformer
ma'adinai mai
|
|
Babban LI/AC
75/28KV
|
|
Sakandare LI/AC
-/3KV
|
|
Impedance
4.5% ± 10% haƙuri
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
1.1 kW< +15% haƙuri
|
|
Akan Rasa Load
10.3 kW< +10% haƙuri
|
|
Jimillar hasara
11.4 W +10% haƙuri
|
|
Launi
Farashin 7035
|
|
Nauyin sashi mai aiki
1070 kg
|
|
Nauyin mai
370kg
|
|
Jimlar nauyi
2200kg
|
1.3 Zane
750 kVA uku lokaci rarraba tasfo zane zane da girman.
![]() |
![]() |
02 Masana'antu
2.1 Kori

Tsarin kewayawa na maganadisu (core) shine ginshikin juyawar wutar lantarki, kai tsaye yana ƙayyade asarar babu-nauyi, ingantaccen aiki, da ƙarfin injina. Wannan taswirar tana amfani da ginshiƙi mai hawa uku, ginshiƙan ƙafafu uku da aka gina daga manyan lamunin ƙarfe na siliki mai ƙarfi.
Masana'antu na zamani suna farawa tare da yanke madaidaicin CNC don rage girman bursu, sannan kuma tari-hannun mataki don rage murdiya da hayaniya. Madaidaicin tari shine mabuɗin sarrafa inganci, yana shafar dogaro kai tsaye na dogon lokaci.
A cikin rahoton gwajin masana'anta, asarar da aka auna ba ta da kaya0.942 kW(a matsa lamba 3) kuma babu-load halin yanzu ne kawai0.53%- duka biyun suna da mahimmanci fiye da ƙimar ƙira, suna tabbatar da ingantaccen kayan mahimmanci da daidaiton tsari.
2.2 Guda
Tsarin iska yana canza makamashin maganadisu zuwa makamashin lantarki. Ingancin sa kai tsaye yana shafar ƙarfin gajeriyar kewayawa, aikin zafi, da amincin rufewa.
Tabbacin Madaidaicin Siga (Kimanin 750 kVA)
|
Gwajin Abun |
Ƙimar Aunawa |
Zane / Daidaitaccen Bukatun |
Hukunci |
|
Adadin rabon wutar lantarki |
-0.11% zuwa +0.00% |
IEC 60076-1 yana ba da damar ± 0.5% |
✔ Wuce |
|
Rashin daidaituwar juriya na HV |
Kasa da ko daidai 0.14% |
Kasa da ko daidai 2% |
✔ Mafi kyau |
|
Rashin daidaituwar juriyar juriya ta LV |
1.03% |
Kasa da ko daidai 2% |
✔ Wuce |
Matsakaicin madaidaicin rabon ƙarfin lantarki shine kawai -0.11%, da kyau a cikin iyakar IEC 60076-1 na ± 0.5% (rahoton gwaji shafi na 5). Rashin daidaituwar juriya na 0.14% (HV) da 1.03% (LV) yana ƙasa da iyakokin masana'antu, yana nuna kyakkyawan ingancin iska da amincin haɗin gwiwa.
A cikin samarwa na zamani, ana amfani da injunan juzu'i ta atomatik ko na atomatik don daidaita tashin hankali na waya, juyowa, da girma. Bayan iska, ana amfani da pre-compaction da siffata don haɓaka ƙarfin injina, tabbatar da mutunci ƙarƙashin gajeriyar kewayawa da zazzagewar zafi.

2.3 Tanko
Wannan na'ura mai rarrabawa kashi uku yana amfani da acikakkar tankin mai da aka rufe(An rufe shi da cikakken mai). Babban fasali:
- An rufe cikakke- Yana rage hulɗar mai-iska, yana rage tsufan mai, yana tsawaita rayuwar sabis.
- Ƙunƙarar ƙuraje- Samar da ingantaccen sanyaya kuma ta atomatik rama canje-canjen ƙarar mai, yana kawar da buƙatar mai kiyayewa daban.
- Shigarwa na waje- Tsayi Kasa da ko daidai da 1000 m, yanayin zafi -25 digiri zuwa digiri +40 .
- Bushings- 3 HV, 3 LV, da 1 LV tsaka tsaki bushings, duk ain, saman-rufe saka.
- Gwajin hatimin matsi- 15 kPa na sa'o'i 24, babu lalacewa ko lalacewa (rahoton gwaji shafi na 7) - mafi kyau fiye da matakan masana'antu na yau da kullum.

2.4 Taron Karshe
Haɗin kai na ƙarshe yana haɗa abubuwan ciki, na'urorin haɗi, da tsarin rufewa. Wannan rukunin ya haɗa da:
|
Na'urorin haɗi |
Qty |
Aiki |
|
Ƙunƙarar ƙuraje |
1 saiti |
Cooling & Mai girma diyya |
|
Magudanar mai / bawul ɗin samfur |
1 |
Kula da mai & Samfur |
|
Multi-aikin matakin ma'aunin mai |
1 |
Tare da aikin taimako na matsa lamba |
|
Mai nuna zafin jiki |
1 |
Kula da zafin mai |
|
Buchholz relay |
1 |
Kariyar kuskuren ciki |
Haɗin kai na zamani yana sarrafa ingancin walda, haɗin flange, da amincin gasket don hana leaks. Na'urorin haɗi suna rufe maɓalli na kariya da ayyukan sa ido, tabbatar da amintaccen aiki na waje.
03 Gwaji
Na'urar rarraba lokaci uku ta wuce duk gwajin IEC 60076 na yau da kullun kafin aikawa. Takaitaccen sakamako:
3.1 Resistance Insulation (Mafi girma ko daidai da 86.8 GΩ - sama da buƙatun al'ada)
|
Matsayin Aunawa |
Resistance Insulation (GΩ) |
Sakamako |
|
HV zuwa LV & ƙasa |
103 |
Wuce |
|
LV zuwa HV & ƙasa |
123 |
Wuce |
|
HV+LV zuwa ƙasa |
86.8 |
Wuce |
3.2 Rarrabe-madogaran Ƙarfin jurewa Gwajin
|
Matsayin Gwaji |
Ƙarfin wutar lantarki (kV) |
Tsawon lokaci (s) |
Sakamako |
|
HV - ƙasa + LV |
28 |
60 |
Wuce |
|
LV - ƙasa + HV |
3 |
60 |
Wuce |
3.3 Gwajin Jure Wutar Lantarki (ACSD)
|
Ƙarfin Wutar Lantarki (bangaren LV) |
Janye da yawa |
Mitar (Hz) |
Tsawon lokaci (s) |
Sakamako |
|
0.83 kV |
2.0 |
150 |
40 |
Wuce |
3.4 Ba a yi hasara & Babu kaya a halin yanzu
|
Matsayin Taɓawa |
Babu kaya na Yanzu (%) |
Asara mara nauyi (kW) |
Sakamako |
|
3 |
0.53 |
0.942 |
Wuce |
3.5 Short-circuit Impedance & Load Loss (an gyara zuwa digiri 75)
|
Iska |
Matsayin Taɓawa |
Tashin hankali (%) |
Asara Load (kW) |
Sakamako |
|
LV |
3 |
4.59 |
9.644 |
Wuce |
3.6 Gwajin Hatimin Matsi
|
Matsa lamba |
Tsawon lokaci |
Sakamako |
|
15 kpa |
awa 24 |
Babu yabo, babu lalacewa |
Ƙarshe:Dukkan gwaje-gwaje na yau da kullun guda tara sun wuce akan ƙoƙari na farko, cikakke gamuwa da IEC 60076-1: 2011. Sakamakon ya tabbatar da ingantaccen ƙirar ƙira, musamman a cikin hatimi, daidaiton rabon wutar lantarki, da ƙarfin dielectric.
04 Shiryawa da jigilar kaya
4.1 Shiryawa
Shiryawa yana biye da daidaitattun hanyoyin fitar da man fetur don injinan mai. Ana jigilar wannan rukuninda mai- kiyaye rufin ciki da hana shigar danshi a lokacin wucewa da kwastam. Kimanin girma: 2100 × 1300 × 1890 mm. Jimlar nauyi kimanin kilogiram . 2200 (zane na ƙarshe don tabbatarwa). Ya dace da daidaitaccen ma'aunin ruwa da kwantena na ƙasa.
4.2 Shipping
- Nauyin jigilar kaya- Don tabbatarwa akan zane na ƙarshe; aika da mai.
- Mai rikodin tasiri- Ba dole ba, amma ana iya sawa tare da mai rikodin tasiri na ɓangare na uku akan buƙata.
- yarda da fitarwa- Zane da kayan aiki suna bin IEC 60076, masu jituwa tare da yawancin ƙayyadaddun grid na duniya.
- Kaya masu haɗari- Mai canza canji abu ne mai haɗari na Class 9; Ana bin marufi na IMDG daidai da sanarwa don fitarwa.
- Zaɓuɓɓukan jigilar kaya- Za a iya jigilar mai cike da mai ko tare da matse mai / nitrogen-blanketed kamar yadda kwangilar ke buƙata.
05 Takaitawa - Tabbacin Ingancin & Abubuwan Haɓakawa
5.1 Yadda Muke Ba da garantin inganci
Tabbacin ingancin yana gudana daga cin albarkatun ƙasa zuwa aika ƙarshe. An tsara masana'antar taswirar rarrabawar zamani zuwa matakai uku: ƙirƙira abubuwan ƙirƙira, taro mai aiki, da taro/gwaji na ƙarshe. Wannan transformer yana biye da tsauraran matakai:
- Dubawa mai shigowa- Babban ƙarfin ƙarfin silicon karfe, waya mai jujjuyawar aluminium, da kayan rufewa ana duba su akan isowa.
- Ikon sarrafawa- Mahimmin matakai (tashin hankali / daidaitawa, ginshiƙan tari, bushewar bushewa) suna da wuraren bincike masu inganci.
- Maganin mai & rufewa- Vacuum mai cike da man fetur da zubar da ruwa, chromatography mai don tabbatar da kaddarorin dielectric; m gwajin hatimi bayan taro.
- Tabbatar da gwadawa- Cikakken gwaje-gwaje na yau da kullun a ƙarƙashin IEC 60076, tare da cikakken rahoton gwaji don tabbatar da aiki.
Waɗannan matakan suna tabbatar da daidaiton samarwa, kwanciyar hankali na lantarki, da dorewar filin lokaci.
5.2 Halayen Masana'antu
- Rufe cikakken zanen mai- Yana rage iskar shaka mai, yana tsawaita rayuwar sabis.
- Karancin asara, babban inganci core- Babu asarar nauyi kawai 0.942 kW (aunawa), babu-nauyi na yanzu 0.53%.
- Tabbatar da ingantaccen gwaji– Duk tara na yau da kullum gwaje-gwaje sun wuce karo na farko; juriya na rufi har zuwa 123 GΩ, wanda ya zarce buƙatu na yau da kullun.
- Cikakken saitin kayan haɗi- Multi-aiki matakin ma'auni mai (tare da matsa lamba), Buchholz gudun ba da sanda, mai zafin jiki nuna alama - lafiya waje aiki.
- IEC 60076 yarda- An tsara shi kuma an gwada shi zuwa IEC 60076; Nau'in zaɓi / gwaje-gwaje na musamman akwai akan ƙarin farashi.
- Amintaccen rufewar muhalli- 24-hour, 15 kPa gwajin matsa lamba - babu zubarwa, babu lalacewa.