20 MVA Substation Mai Canjin Wuta-33 / 6.65 kV|Afirka ta Kudu 2025

20 MVA Substation Mai Canjin Wuta-33 / 6.65 kV|Afirka ta Kudu 2025

Ƙasar Bayarwa: Afirka ta Kudu 2025
Yawan aiki: 20MVA
Wutar lantarki: 6.65kV
Fasalin: Tayafu huɗu (ton 10)
Aika Aikace-aikacen

 

20MVA-33/6.65kV step down power transformer

20 MVA Substation Power Transformer - Dogaran Powerarfin Ma'adinan Ma'adinai

 

01 Gabaɗaya

1.1 Bayanin Aikin

Wani abokin ciniki na Afirka ta Kudu ya ba da umarnin a20MVA-33/6.65kV mataki saukar da wutan lantarkia watan Mayu 2025. Abokin cinikinmu yana samar da tasfoma, ƙananantashoshin sadarwada igiyoyin wutar lantarki zuwa ma'adanai na gida da na waje. Wannan transfomar kuma yana ɗaya daga cikin manyan injiniyoyin da aka keɓance don tashoshin ma'adinai. Kasar Afirka ta Kudu dai na daya daga cikin kasashen da suka ci gaba a fannin hakar ma'adinai, kuma ana bukatar taransfoma na ma'adinai.

Wannan matakin rage wutar lantarki ya ɗauki IEC 60076{10}}1:2011 misali. Yana ɗaukar hanyar sanyaya ONAN. Ƙungiyar Waya: YNyn0, dace da yanayin ƙasa mai rikitarwa. Kayan da ke jujjuyawa shine jan karfe, kuma asarar jan ƙarfe yana ƙasa. An ƙididdige shi a 33kV a gefen farko da 6.65kV a gefen sakandare. An sanye shi da mai sauya matsa lamba (OLTC) tare da kewayon tsari na ± 10 × 1%, yana ba da damar daidaita wutar lantarki a ƙarƙashin kaya, yana tabbatar da ingantaccen wutar lantarki ga kayan aikin hakar ma'adinai. Na'urar taswirar wutar lantarki tana samun kyakkyawan aikin makamashi, ba tare da asarar nauyi na 13.65 kW ba, asarar nauyi a digiri 75 na 132.8 kW, da kuma asarar gabaɗaya zuwa 72 kW. Don inganta motsi, musamman a wuraren hakar ma'adinai masu nisa, an ƙera na'urar taransifoma tare da manyan ƙafafu masu nauyi, fasalin da ke sauƙaƙa ayyukan yanar gizo.

Me yasa Ya dace don Aikace-aikacen Ma'adinai

A cikin ayyukan hakar ma'adinai, ingantaccen ingantaccen wutar lantarki yana da mahimmanci don tabbatar da aminci da yawan aiki. Wannan na'ura mai sarrafa wutar lantarki ya dace da yanayin rarraba wutar lantarki na ma'adinai:

Matsakaicin Fasa: Matakan ƙasa 33kV daga grid mai amfani ko tashoshin wutar lantarki zuwa 6.6kV, daidaitaccen ƙarfin lantarki don kayan aikin hakar ma'adinai.

Underground Power Delivery: Transmits 6.6kV power through cables to underground systems - an ideal voltage for long-distance transmission with low losses.

Babban -Aikin Kayan Aikin Wuta: Yana ba da iko mai nauyi{1}} injunan hakar ma'adinai kamar injinan ƙwallo, masu ɗaukar hoto, masu ba da iska, da famfunan cire ruwa.

 

 

 

1.2 Ƙayyadaddun Fasaha

20MVA substation ikon wuta dalla-dalla da bayanai takardar

Isarwa zuwa
Afirka ta Kudu
Shekara
2025
Nau'in
Mai nutsar da wutar lantarki
Daidaitawa
IEC 60076-1: 2011
Ƙarfin Ƙarfi
20 MVA
Yawanci
50HZ
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
33 kv
Na biyu Voltage
6.65 kV
Abubuwan Iska
Copper
Matsala ta kusurwa
YNyn0
Impedance
10%
Matsa Canji
OLTC
Taɓa Range
±10*1
Babu Asara Load
13.65 kW
Load asarar a 75 digiri
132.8 kW
Jimillar hasara
72 kW

 

 

1.3 Zane

20MVA tashar wutar lantarki zane da farantin suna

20 MVA substation power transformer drawing 20MVA  substation power transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Taswirar wutar lantarki tana da ginshiƙi - mataki uku{1}}, wanda aka nuna a cikin hoton yayin da mai fasaha ke cire karkiya ta sama. An yi ainihin sa da sanyi{3}} hatsi na birkiyya{4}} silikon karfe mai daidaitacce, wanda ke ba da kyawawan kaddarorin maganadisu tare da jujjuyawa{5}madaidaicin aikace-aikacen taswira. Don ci gaba da rage asarar kaya, ana amfani da gaɓoɓin gaɓoɓin (mataki{8}}) ​​don daidaita juzu'in maganadisu tare da jujjuyawar ƙarfe, haɓaka ingantaccen aiki gabaɗaya.

20 mva substation power transformer-three-phase three-limb core

 

2.2 Guda

Na'urar wutar lantarki ta YNyn0 tana ɗaukar tsarin jujjuyawar diski mai ci gaba don duka manyan iskar wutar lantarki da ƙarancin ƙarfi. Ci gaba da jujjuyawar diski yana ba da kyakkyawan aikin sanyaya axial kuma ya dace musamman don manyan aikace-aikace{4}} na yanzu, babba{5}. Kowane iska yana fuskantar tsauraran magani, Layer{7}} ta{8}} bushewar Layer, da sarrafa juzu'i don tabbatar da daidaito da ƙarfi.

20 MVA substation power transformer YNyn0 power transformer winding
20 MVA substation power transformer Voltage regulating winding
20 MVA YNyn0 substation power transformer winding

 

2.3 Tanko

20 MVA substation power transformer oil tank

Tankin mai mai karfin wutar lantarki na MVA 20 dole ne a yi gwajin zubar da jini kafin ya bar masana'anta. An ƙera duk welds, haɗin gwiwar flange, da sansanonin bushing don tabbatar da dogon{2}} amintaccen hatimi. An karɓi nau'in radiyo{4}}waɗanda za a iya cirewa, kuma ana shigar da tayoyin tan guda huɗu na ton 10{6} a ƙasa don sauƙin motsi a wurin. Ana ba da rami a gefen tanki don sauƙaƙe dubawa na ciki da kuma kula da kayan aiki.

 

2.4 Taron Karshe

1. An haɗa ɓangaren aiki na na'urar lantarki a cikin hoton, kuma mai gwadawa yana yin gwaje-gwajen aikin lantarki na yau da kullum.

2. Ana ɗaga ɓangaren aiki a cikin tanki.

3. Shigar da wasu sassa: mai nuna zafin jiki mai nuna alama, bawul ɗin taimako na matsa lamba, mai nuna alamar man fetur, iskar gas, mai numfashi, tashar ƙasa, akwatin tashar, Wheels (10T).

4. Zuba mai a cikin tankin transfoma don cika sararin ciki na na'urar da kuma tabbatar da cewa matakin mai ya cika bukatun.

5.Saboda babban wurin da na'urar radiyo ta mamaye, za'a hada ta kafin a fara gwajin sannan a kwashe a kwashe domin sufuri bayan gwajin.

20 MVA substation power transformer active part

 

 

03 Gwaji

Tsarin Gwaji

1. Auna narkar da iskar gas a cikin dielectric ruwa daga kowane keɓaɓɓen sashin mai ban da juzu'in sauyawa

2. Auna Girman Wutar Lantarki da Duba Matsugunin Mataki

3. Bincika ragi da ƙaƙƙarfan ginshiƙan da aka gina{1} a cikin tasfofi na yanzu

4. Ma'aunin juriya na iska

5. Ma'auni na Ƙwararren Ƙwararren Ƙwararru

6. Gwajin Karfin Wutar Lantarki

7. Auna A'a -Asarawar Load da Yanzu

8. Gwada Akan Masu Canjin Taɓa - Gwajin Aiki

9. Gwajin Ƙarfin Wutar Lantarki

10. Auna Gajeren -Cikin Tasirin kewayawa da Rasa Load

11. Insulation na ƙarin wayoyi (AuxW)

12. Gwajin Leak tare da Matsi don Liquid{1}}Masu Canjin Ruwa

 

 

04 Shiryawa da jigilar kaya

20 MVA substation power transformer packing
20 MVA substation power transformer shipping

 

05 Yanar Gizo da Takaitawa

Wannan matakin 20MVA{3}33/6.65kV{10} saukar wutar lantarki an yi shi ne don aikin haƙar ma'adinai. Yana da ƙarfi, inganci, kuma mai sauƙin motsawa. Tare da IEC 60076-1: 2011 yarda, ingantattun iskar tagulla, da ingantaccen tsarin ka'idojin OLTC. Yana ba da ƙarfi da sassaucin ƙarfi don hakar ma'adinai. Tankin yana da ƙarfi, ana iya cire radiators, kuma ƙafafun suna da nauyi. Wannan yana sauƙaƙa amfani da shi a wurare masu nisa.

Yana da ƙananan hasara, babban inganci, kuma yana da sauƙin ɗauka. Wannan yana nuna burin mu don baiwa abokan cinikin ma'adinai kayan aikin da suka dace da ma'auni kuma suna kiyaye aiki lafiya da inganci. Hako ma'adinai a Afirka ta Kudu na karuwa cikin sauri. Muna alfaharin tallafawa abokan aikinmu tare da ingantattun hanyoyin samar da wutar lantarki waɗanda ke ci gaba da gudanar da ayyuka cikin sauƙi a yau da kuma nan gaba.

20MVA-33/6.65kV step-down power transformer

 

 