112.5 KVA Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararrun Ƙwararrun Ƙwararru na 3-13.8 / 0.208 KV|Kanada 2025
Yawan aiki: 112.5 kVA
Wutar lantarki: 13.8D-0.12/0.208kV
Feature: tare da mai nuna alama matakin
Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin masana'antun da suka fi dacewa kuma masu samar da 112.5 kva pole wanda aka ɗora 3 zamani tasfoma ({7}}13.8/0.208 kv|kanada 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

Tsayawa Sama, Ƙarfafa Rayuwa a ƙasa. Amintattun Pole Dutsen Transformers.
01 Gabaɗaya
1.1 Bayanin Aikin
112.5 kVA uku fangai mai sandar wutan lantarki da aka ɗora zuwa Kanada a cikin 2025. Ƙarfin wutar lantarki shine 112.5 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 13.8D kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.12 / 0.208 kV, sun kafa ƙungiyar vector na Dyn1.
Wannan 112.5kVA uku -ƙara{2}}wanda aka ɗora tafsiri shine babban na'urar juyawar wutar lantarki mai ƙarfi a matsakaici{4}}ƙananan hanyoyin rarraba wutar lantarki, wanda ke aiki azaman maɓalli na rarraba ga tashoshin rarraba hanyoyin sadarwa na birane, rassan wuraren shakatawa na masana'antu, da tsarin samar da wutar lantarki mai nisa. Yana ɗaukar tsarin shigarwa na dakatarwa{6}, sanye take da takamaiman anti-lalata da tsatsa{9}}hujja da aka rufe da kuma 13.8kV-jikin insulation na aji, waɗanda suka dace da tura layin sama a tsayi. Ana saita canjin tsarin wutar lantarki akan babban gefensa na ƙarfin lantarki, yana ba da damar ±2*2.5% lafiyayyan wutar lantarki{16}}sarrafa don daidaitawa da jujjuyawar grid da kuma tabbatar da ingantaccen ƙarfin mai amfani-.
Tare da ƙididdige ƙarfin 112.5kVA, yana goyan bayan 13800V matsakaici{2}}shigarwar ƙarfin lantarki da ƙarancin ƙarfin 208V/120V{5}}ƙarfin ƙarfin lantarki. Ƙarƙashin sharadi -lokaci guda uku, yana iya ɗaukar kimanin{8}}Aikin da aka ƙididdige shi akan ƙaramin{9}}ƙarfin wutar lantarki{10}mai ikon samar da wutar lantarki na zamani guda uku don kayan aikin masana'antu, yayin da kuma saduwa da buƙatun wutar lantarki guda ɗaya{12} ga masu amfani da kasuwanci da na zama. Ingancin jujjuyawar wutar lantarki ya wuce 98.74% a ƙarƙashin ƙimar da aka ƙididdige shi, yadda ya kamata yana rage asarar wutar lantarki a cikin hanyar rarrabawa.
Wannan na'urar na'urar lantarki yana da amfani ga al'amuran da suka haɗa da sabunta hanyoyin sadarwa na rarraba birane (masu warware matsalolin da suka wuce gona da iri a tsoffin wurare), rarraba reshen wuraren shakatawa na masana'antu (goyan bayan ci gaba da samar da wutar lantarki ga ƙanana da matsakaita{0}masu girma), kewayon samar da wutar lantarki na yanki mai nisa (cika gibin wutar lantarki a yankunan karkara da kewayen birni), da yanayin wutar lantarki na wucin gadi (kamar manyan gine-gine da abubuwan da suka faru a waje). Idan aka kwatanta da na'urorin lantarki masu hawa -, ba wai kawai tana adana sararin ƙasa ba har ma yana inganta aiki da aminci ta hanyar nisantar wuraren ayyukan ma'aikata. Babban matakin rufewa da ƙirƙira ƙira na lalata yana ba da damar rayuwar sabis na waje sama da shekaru 20, yana rage tsayin lokaci{6}} aiki da tsadar kulawa. A halin yanzu, aikin ka'idojin wutar lantarki na iya rage tasirin sauyin wutar lantarki akan ainihin kayan aiki, yana mai da shi babban zaɓi don haɓaka hanyar sadarwar rarraba tare da ƙaƙƙarfan ƙarfi, babban abin dogaro, da daidaita yanayin yanayin.
1.2 Ƙayyadaddun Fasaha
112.5 kVA iyakacin duniya saka taswira bayani dalla-dalla irin da bayanai takardar
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Pole mounted transformer
|
|
Daidaitawa
CSA C2.2-06
|
|
Ƙarfin Ƙarfi
112.5 kVA
|
|
Tsayi
Kasa da ko daidai da 1000m
|
|
Yawanci
60HZ
|
|
Mataki
1
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
13.8d kV
|
|
Na biyu Voltage
0.208 / 0.12 kV
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
3.5%
|
|
inganci
Yafi ko daidai 98.74%
|
|
Matsa Canji
±2*2.5%
|
|
Babu Asara Load
0.475 kW
|
|
Akan Rasa Load
1.06 kW
|
|
Launi
ANSI Grey70#
|
1.3 Zane
112.5 kVA sandar sandar da aka ɗora hoto da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Tanki

Wannan shi ne tanki na 112.5kVA guda uku -ƙarar sandar zamani{2}}wanda aka ɗora tasfoma, an ƙera shi daga ƙarfe mai ƙarfi kuma a cikin ƙaramin ƙarfe{3}}ƙarshen samarwa (tare da shafa mai launin toka). Yana da tsari mai waldadi na rectangular: saman ya haɗa da musaya don abubuwan da aka gyara na kayan wuta, yayin da buɗe madauwari guda 4 na gaba an tanada don wayoyi/na'urorin haɗi. Haɗe tare da murfin da aka rufe (wanda aka gani a kusa), zai ƙunshi sassa na ciki, yana riƙe da mai mai rufi (don rufi da zafi mai zafi), da kuma kare abubuwan ciki bayan cikakken taro.
2.2 Taron Karshe
Wannan shine wurin taro na ƙarshe na 112.5kVA guda uku -ƙarar sandar zamani{2}}wanda aka ɗora tasfoma, tare da aikin walda wayar gubar a halin yanzu. Ana iya gani anan ainihin abubuwan da suka haɗa da na'urar wutar lantarki (ciki har da iska guda uku - wanda aka naɗe da farar rufi), kuma wani ma'aikaci yana sarrafa wayoyi masu ƙyalli na jan ƙarfe{5} yana walda su don haɗa iskar da tashoshi na waje (maɓalli mai mahimmanci don tabbatar da ingantaccen watsa wutar lantarki). Kayan aikin gama gari na gama gari (kamar almakashi da wrenches) suna kwance a kusa; wannan haɗin wiring yana da mahimmancin hanyar haɗin lantarki a cikin taron ƙarshe, yana shimfiɗa harsashi don rufewa na gaba da gwajin aiki.

2.3 Na'urar Taimakon Matsi

Na'urar taimakon matsa lamba da aka sanya akan wannan 112.5kVA guda uku -ƙara mai ƙarfi{2}}wanda aka ɗora tafsiri shine mahimmin kayan kariya da aka tsara don fitar da iskar gas da ke haifarwa cikin gaggawa a yayin da wani mummunan lahani na ciki ko kuma ya wuce kima. Yana aiki azaman rashin tsaro na inji, yana kunna nan take don hana fashewar tanki mai bala'i ta hanyar sakin matsa lamba ta hanyar tashar iska mai keɓe, ta haka yana rage haɗarin wuta, fashewa, da lalacewar kayan aiki. Yawanci yana nuna tuta na gani ko mai nuna alamar aiki, na'urar tana taimakawa wajen kare amincin tsarin na'urar da kuma tabbatar da amincin kayan aikin da ma'aikata da ke kewaye. Da zarar an kunna shi, yana buƙatar binciken hannu da sake saiti yayin kulawa na gaba.
2.4 Matsa Canji
Canjin famfo sanye take da wannan 112.5kVA guda uku -sanarwar lokaci{2}}wanda aka ɗora tasfoma shine daidaitaccen WSLⅡ3 63/20{6}}6×5 kashe{7}} nau'in kewayawa, na'urar haɗaɗɗiya ta duniya da aka ƙera don mai{9}} na'ura mai ba da hanya tsakanin hanyoyin sadarwa maimakon naúrar al'ada. An shigar da shi akan babban ɓangaren wutar lantarki{15} na taransfoma, yana da ƙididdigan ƙarfin lantarki na 20kV da ƙididdigan halin yanzu na 63A, tare da matsayi 5 na taɓawa waɗanda ke ba da damar ±2 × 2.5% na kewayon ƙayyadaddun wutar lantarki{17} samun daidaitawar wutar lantarki ta hanyar canza adadin juyi na farko. A matsayin mahimmin sashi don daidaita ƙarfin lantarki, dole ne a yi aiki da shi lokacin da aka ba da ƙarfin wutar lantarki don tabbatar da sauyawa mai aminci, daidaitaccen ramawa ga jujjuyawar wutar lantarki da kiyaye daidaitaccen fitarwa mai ƙarancin wuta ga masu amfani da ƙarshe.
Ƙaƙƙarfan ƙira ɗin sa ya dace da sandar gidan wuta na waje{0}sake aiki, yana jure matsananciyar yanayin muhalli tare da tabbatar da ingantaccen aiki cikin dogon lokaci{1}}.

2.5 Alamar Matsayin Mai

Alamar matakin mai ita ce madaidaicin samfurin UHZ{1}01, kayan haɗi na duniya wanda aka ƙera don matsakaita da ƙanana{2}}mai girman mai-waɗanda aka nutsar da su maimakon naúrar al'ada. An shigar da shi a tsaye a gefen ma'ajin mai na transfoma, yana aiki bisa ka'idodin buoyancy da haɗin gwiwar maganadisu: wani ruwa na ciki yana motsawa daidai da matakin mai, yana tuƙi mai nuna alama a sarari don nuna matakin ruwa mai maye gurbin ma'aunin bututun gilashin gargajiya tare da ingantaccen aminci, ganuwa, da dorewa. Injiniya don jure matsananciyar yanayi na waje, yana fasalta kewayon zafin jiki mai faɗi na -40 digiri zuwa digiri 80, yana dacewa da yanayin zafi har zuwa 90% (a digiri 25), kuma yana aiki da dogaro a tsayin ƙasa ƙasa ko daidai da 2000m ba tare da tasirin girgiza mai ƙarfi ko filaye mai ƙarfi ba. A matsayin muhimmin bangaren sa ido, yana ba ma'aikatan kulawa da sauri su duba matsayin matakin mai, tabbatar da isassun injunawa da aikin kashe zafi na na'urar da kuma tallafawa magance matsala na lokaci don guje wa haɗarin aiki da ke haifar da ƙarancin mai ko ambaliya.
2.6 Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙwara
Ƙarƙashin ƙarancin wutar lantarki na wannan 112.5kVA guda uku -ƙaran sandar zamani{3}}wanda aka ɗora tasfoma shine madaidaicin ƙirar 251101-12XD.401.004.B, na'urorin haɗaɗɗen mai na duniya- immersed transformers. An ɗora shi a gefen tanki, an yi shi da fiber na gilashin{9}}ƙarfafawar polyester mai ƙarfi don juriya mai ƙarfi, dacewa da sandar sandar waje{15}}ayyukan da aka ɗora. Wanda aka ƙididdige shi don fitarwa na 208V/120V na taransfoma tare da Mafi Girma ko daidai da ƙarfin 200A na yanzu (wanda ya zarce ƙarancin ƙimar 158A{16}}ƙaramar ƙimar ƙarfin ƙarfin lantarki), yana da faren tin{19}} tashoshi na tagulla don ingantaccen haɗin gwiwa. Yin biyayya da ka'idodin rufin 1.2kV da sanye take da hatimin ƙwanƙwasa, yana watsa ƙananan ƙarfin wuta cikin aminci yayin da yake kare abubuwan ciki.

2.7 Babban -Busar Wutar Lantarki

Babban -ƙarar wutar lantarki na wannan 112.5kVA uku -ƙaran sandar zamani{3}}wanda aka ɗora tasfoma shine madaidaicin ƙirar 12XD.401.010-A, na'urorin haɗaɗɗen mai na duniya{12}}waɗanda aka nutsar dasu. An ɗora shi a kan tankin, yana fasalta jikin rufin ain da tashoshi, wanda aka ƙididdige 18KV/55A tare da nisa mai rarrafe Mafi girma ko daidai da 450.85mm da 125KV ƙarfin ƙarfin walƙiya, yana tabbatar da babban amintaccen watsa wutar lantarki don ayyukan da aka saka na waje.
03 Gwaji
Wannan 112.5kVA guda uku -ƙara{2}} wanda aka ɗora wutar lantarki (samfurin: 112.5kVA-13.8DELTA-0.208/0.12kV) yayi gwaje-gwaje na yau da kullun akan CSA C2.1-06(R2022) da CSA C802.2022 (R2022) da CSA C802.2022 (R2022) jure gwajin, gwajin juriya, da gwajin yatsa na 24h a 20kPa. Duk abubuwan sun wuce: inganci ya kai 98.94%, juriya na rufi ya cika buƙatu, babu ɗigowa da ya faru, kuma maɓalli masu mahimmanci kamar asarar nauyi da ƙarfin ƙarfin ƙarfi sun bi ƙayyadaddun bayanai.


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
A matsayin babban na'urar rarraba wutar lantarki mai ƙarfi{0}madaidaita daidai da ƙa'idodin CSA na ƙasa da ƙasa (CSA C2.1{6}}06(R2022) & CSA C802.1-13(R2022)) kuma ingantaccen ingantaccen gwaje-gwaje na yau da kullun, wannan 112.5kVA ya tsaya tsayin daka{1} tare da ingantaccen juzu'i na 98.74%, ingantaccen aikin fitarwar wutar lantarki, da ƙirar kariya ta waje mai ƙarfi. Ya dace daidai da yanayin yanayi daban-daban kamar sabunta hanyar sadarwar rarraba birane, samar da wutar lantarki na masana'antu, da kewayon wutar lantarki. Haɗa kariyar rufin da aka yarda da ita, daidaitaccen tsarin wutar lantarki, dogon{13}}ƙara mai ɗorewa-lalata, da ƙarancin aiki da tsadar kulawa, ba wai kawai yana biyan madaidaicin buƙatun masu amfani don kwanciyar hankali ba amma kuma ya yi daidai da makamashi{17}} ceton manufar haɓaka hanyar sadarwa. Abin dogaro, babban aiki, da mafita na rarraba wutar lantarki, yana ba da ci gaba da goyan bayan wutar lantarki don yanayin aikace-aikacen ƙananan ƙarfin lantarki daban-daban.

Hot Tags: sandar sandar ɗora 3 zamani masu canza wuta, masana'anta, mai kaya, farashi, farashi
You Might Also Like
25 kVA Pole Dutsen Mai Canjin Mataki na Uku-5.5 / 0....
75 kVA 3 Mai Canja Wuta na Fashe-13.8 / 0.22 kV|Guya...
1500 kVA Kushin Dutsen Mai Canjawa-13.8 / 0.46 kV|Gu...
1000/1150 kVA Rarraba Mai Canjawa Substation-13.8 / ...
25 kVA Kushin Haɗa Mai Canjawa-24*12 / 0.24 kV|Jamai...
300 kVA Kushin Haɓaka Masu Canjin Lantarki-34.5 / 19...
Aika Aikace-aikacen