75 kVA 3 Mai Canja Wuta na Fashe-13.8 / 0.22 kV|Guyana 2024
Yawan aiki: 50kVA
Wutar lantarki: 13.8/0.22kV
Feature: tare da OCTC

Ƙwararru da Amintacce, Ingantacciyar Samar da Wutar Lantarki - Uku{1}}Poli mai ɗaure{2}, yana tabbatar da ingantaccen ƙarfi ga kowace kilowatt{3}}awa.
01 Gabaɗaya
1.1 Fagen Aikin
An isar da tasfoma mai nauyin 75 kVA uku na sandar sandar wuta zuwa Guyana a cikin 2024. Matsakaicin ƙarfin injin ɗin shine kVA 75. Babban ƙarfin lantarki na na'urar shine 13.8 kV kuma ƙarfin lantarki na biyu shine 0.22 kV. Ƙungiyar haɗin gwiwar shine Dyn1, kuma sanyaya shine ONAN. Motocin da aka ɗora sandar igiya guda uku da SCOTECH ke samarwa suna da ingantaccen tsarin rufewa da ƙarfin tasirin walƙiya. Rarraba juzu'i na Uniform, ƙaramar ƙarin hasara, babu wani abu mai zafi na gida. Ƙananan ƙarfin lantarki, ƙaramar girgiza da amo. Rarraba yawan zafin jiki daidai ne kuma tasirin sanyaya yana da kyau. Siffar maganadisu tana da babban layin layi da babban haɗin layin layi.
Our 150 kVA uku lokaci iyakacin duniya saka tasfo an ƙera shi da ci-gaba fasaha da kuma rungumi high quality abu da aka gyara wanda ya haifar da ingantacciyar inganci da dogon aiki lokaci. Muna ba da garantin cewa kowane tafsirin da muke bayarwa ya wuce cikakkiyar gwajin karbuwa don tabbatar da babban aiki da aminci. Daga tuntuɓar farko da zance zuwa masana'anta, shigarwa, ƙaddamarwa, horo, da kuma bayan tallafin tallace-tallace, muna ba da cikakkiyar mafita ta maɓalli. A halin yanzu na'urorin tasfoman mu suna cikin kwanciyar hankali a cikin ƙasashe sama da 50 a duniya. Da himma ga inganci da sabis, muna ƙoƙari mu zama amintaccen mai samar da taswirar ku kuma abokin kasuwanci na dogon lokaci-.
1.2 Ƙayyadaddun Fasaha
75 kVA uku lokaci iyakacin duniya saka tasfo bayani dalla-dalla da bayanai takardar
|
Isarwa zuwa
Guyana
|
|
Shekara
2024
|
|
Nau'in
Fuskar Fuskar Wuta Mai Fuska Uku
|
|
Daidaitawa
IEEE C57.12.00-2021
|
|
Ƙarfin Ƙarfi
75kv ku
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Launi
ANSI Grey70#
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
13.8 kV
|
|
Na biyu Voltage
0.22 / 0.127 kV
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
2%
|
|
Hakuri
±7.5%
|
|
inganci
Yafi ko daidai 98.63%
|
|
Taɓa Range
± 2 * 2.5% @ gefe na farko
|
|
Core Material
Silicon karfe takardar hatsi daidaitacce
|
|
Liquid insulant
PCB free Transformer Mineral Oil
|
|
Babu Asara Load
Kasa da ko daidai da 0.32KW
|
|
Akan Rasa Load
Kasa da ko daidai da 0.98KW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
75 kVA uku na sandar sandar sandar da aka ɗora taswirar zane da girma.
![]() |
![]() |
02 Masana'antu
2.1 Kori
An yi ainihin abin sanyi mai inganci{1} silikon karfe na birgima, kyakkyawan layin juzu'i na cikin gida, shear burr<0.02, full oblique joint, no punching, no stacking iron wheel process; The double H adhesive makes the three columns of the core become a tight, flat and compact whole, effectively reducing the no-load loss, no-load current and noise of the transformer.

2.2 Guda

Tushen wutan lantarki yana ɗaukar wayar aluminium mai tsafta mai tsayi{0}, wanda ke rage asara yadda ya kamata, pad da tsayawa suna zagaye, filin lantarki iri ɗaya ne, kuma amincin yana ƙaruwa. Ana ƙarfafa goyon bayan iska na ciki don inganta kwanciyar hankali da kuma hana rashin daidaituwa da lalacewa.
Gilashi mai jujjuyawar ya ƙunshi zanen gado mai kama da juna, yawanci da jan karfe ko aluminum. Waɗannan tsare-tsare an ware su a waje kuma an haɗa su don samar da tsarin iska.
Wannan zane ya sa da tsare winding iya mafi alhẽri zafi dissipation a lokacin da hõre high halin yanzu, amma kuma rage juriya da inductance na winding, da kuma inganta lantarki yi na winding. Babban abin da ke tattare da jujjuyawar foil shi ne cewa an yi shi a kan na'ura mai jujjuyawa na musamman, wanda ke da babban matakin sarrafa kansa kuma yana ba da babban aiki da ingancin samfur. Juyawa, wato, interlayer da longitudinal capacitance babba ne, an kawar da kusurwar karkace, gajeriyar juriyar tasirin kewayawa tana da ƙarfi, ƙarfin injin yana da girma, ginin ya dace, kurakuran axial da radial ƙanana ne, girman geometric yana da sauƙi don tabbatarwa, jujjuyawar tana da matsatsi, ba sauƙin samun kumfa ba. Hakanan iskan foil na iya rage juzu'i da haɓaka aikin rufewar iskar.
2.3 Tanko
Don ainihin tsarin rufewa na gargajiya na gargajiya, musamman inda mai yayyan mai yana da sauƙin faruwa, fara daga sarrafa siyan kayan don tabbatar da cewa ƙarfe ba ya yi tsatsa, karo, karce, guduma, aiki na musamman na ɓangaren hatimin tankin mai, da zanen gabaɗaya na akwatin, cire kaifi kusurwar burrs da waldi slag da aka haifar a cikin sarrafa akwatin, da ƙarfafa mannewar fenti.

2.4 Taron Karshe


03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin rashin daidaiton juriya ƙasa da ko daidai da 4% |
0.43 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
-0.08~-0.01 |
Wuce |
|
3 |
Mataki - Gwaje-gwajen alaƙa |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -Asar lodi da tashin hankali Yanzu |
% kW |
I0 : bayar da ma'auni darajar P0: ba da ƙima mai ƙima juriyar rashin hasara shine +0% |
1.21 0.266 |
Wuce |
|
5 |
Haɓaka Haɓaka Ƙarfin Wutar Lantarki da Inganci |
% kW kW |
t:85 ku Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +0% Ingancin ba kasa da 98.74% |
2.17 0.832 1.098 98.80 |
Wuce |
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV/: 34kV 60s LV/: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (kV): 2 Ur Duration(s): 48 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Ground: LV -HV zuwa Ground: HV&LV zuwa Ground |
53.4 50.6 48.8 |
/ |
|
10 |
Gwajin Dielectric Oil |
kV |
Yafi ko daidai da 45 |
52.83 |
Wuce |


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
Na gode don ba da lokacin don koyo game da Tushen mu guda ɗaya -Phase Pole-Mounted Transformer! A cikin tsarin wutar lantarki na zamani, samfuranmu ba kawai ingantaccen na'urar samar da wutar lantarki ba ne har ma da ƙaƙƙarfan ginshiƙi don tabbatar da aikin wutar lantarki. Mun himmatu don samar da hanyoyin da aka keɓance ga abokan cinikinmu, haɗa ingantaccen fasaha tare da ra'ayoyi masu alaƙa da muhalli don ba da damar watsa makamashi mai inganci. Zaɓin mu yana nufin zabar tabbataccen ƙarfin iko don nan gaba. Muna fatan yin aiki tare da ku don gina mafi wayo kuma mafi dorewa zamanin makamashi tare!

Hot Tags: 3 lokaci iyakacin duniya transformer, manufacturer, maroki, farashin, farashi