01 Gabaɗaya

1.1 Fagen Aikin

An kai 2000 kVA substation transformer zuwa Kanada a cikin 2025. Ƙarfin wutar lantarkin shine 2000 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 44 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.48Y/0.277 kV, sun kafa ƙungiyar vector na Dyn1.

Tare da sassauƙan ƙira da ingancin masana'anta, masu canza canjin da SCOTECH ke samarwa daidai da cika buƙatun abokin ciniki iri-iri. Baya ga isar da amintaccen jujjuyawar wutar lantarki da rarrabawa, waɗannan na'urori suna fasalta ƙira na ci gaba don rage haɗarin arc flash da rage tasirin muhalli. Ana iya keɓance su zuwa takamaiman yanayin aiki, gami da daidaitawa zuwa keɓancewar mahallin aiki, tsayin yanayi{2}, da takamaiman buƙatun inganci. Masu amfani kuma za su iya zaɓar daga zaɓuɓɓukan haɗin kai iri-iri, kamar saman -mai hawa ko bangon gefe{5}}ananan bushings, yana tabbatar da haɗin kai mara kyau cikin tsarin rarraba firamare ko na sakandare.

Ko don grid na birni, wuraren wutar lantarki na masana'antu, ko manyan ayyukan samar da ababen more rayuwa, na'urori masu rarraba wutar lantarki suna samar da ingantacciyar hanyar sarrafa makamashi mai aminci, da aminci ga muhalli{0}masu hidima a matsayin ginshiƙin hanyoyin sadarwa na zamani.

 

 

1.2 Ƙayyadaddun Fasaha

2000 kVA na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takaddun bayanai

Isarwa zuwa
Kanada
Shekara
2025
Nau'in
Taranfoma na Substation
Daidaitawa
CSA C88:16
Ƙarfin Ƙarfi
2000kVA
Yawanci
60HZ
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
44 kv
Na biyu Voltage
0.48 kV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
Dyn1
Impedance
6%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
2.15 kW
Akan Rasa Load
18.6 kW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

2000 kVA substation mai canzawa zane zane da girman.

2000 kVA distribution substation transformer drawing 2000 kVA distribution substation transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Tsarin asali gama gari sun haɗa da ƙirar ƙafa uku{0}}fashi na uku{1}}ƙafa da uku{2}}tsari biyar{3}}tsari. Ana amfani da ginshiƙin ƙafa uku - kashi uku - ginshiƙan ƙafafu don ƙaƙƙarfan tsarinsa da tsadarsa{7}} tasiri, yayin da uku{8}}sashi na biyar- core ƙafa yana ba da kwanciyar hankali mafi girma da ƙananan ɗigogi, dacewa da ƙarin hadaddun buƙatun wutar lantarki.

Cores na transformer yawanci suna fasalta tsararren gyare-gyaren da aka ƙera don rage asara na yau da kullun ta cikin zanen ƙarfe na bakin ciki. Ana amfani da kayan inganci masu inganci kamar silikon karfe, manyan silikin alloys, da kuma karfen lantarki marasa dacewa don inganta ƙarfin maganadisu da rage asara. Kyawawan ƙira ba wai yana haɓaka kwanciyar hankali da inganci a ƙarƙashin yanayin aiki daban-daban ba har ma yana rage farashin aiki da ƙarfafa juriyar injin na'urar zuwa gajerun hanyoyin kewayawa da lodi.

 

2.2 Guda

2000 kVA distribution substation transformer wire winding

Na'ura mai ba da wutar lantarki tana amfani da daidaitawar coil rectangular, wanda ya haɗa da waya{0}maɗaukakin rauni{1}}ƙarar wutar lantarki na farko da takarda{2}}rauni na biyu. Wannan ƙwaƙƙwaran ƙira yana rage damuwa axial daga gajerun da'irori yayin da yake tabbatar da ingantacciyar ma'aunin maganadisu na haɗin famfo.

An ƙera coils ɗin da daidaito ta hanyar amfani da injina na ci gaba, wanda ke ba da damar sarrafa tashin hankali da ingantacciyar madaidaicin wurin madugu, ta haka yana haɓaka ƙarfin kewayawa da ingantaccen aiki. Babban -lu'u lu'u-lu'u mai inganci-epoxy-mai rufin takarda ana amfani da shi a ko'ina cikin iska, yana samar da ingantaccen tsarin tsari da ingantaccen rufin lantarki a wuraren damuwa masu mahimmanci. Wannan sabon ƙira yana sauƙaƙe ingantacciyar zagayawa na ruwa mai sanyaya, yana kiyaye mafi kyawun yanayin aiki.

Majalisun Coil suna fuskantar matsanancin zafi{0}}tsarin warkarwa a ƙarƙashin ƙididdige matsi na hydraulic a hankali, yana ƙarfafa abubuwan da za su iya jure ƙarfin da aka haifar yayin gajeriyar kewayawa. Wannan ƙwararren injiniya yana tabbatar da cewa coils na lantarki suna ba da kyakkyawan aiki da aminci, yana ba da gudummawa sosai ga daidaiton tsarin rarraba wutar lantarki gaba ɗaya.

 

2.3 Tanko

An ƙera tankuna masu canzawa don ƙaƙƙarfan ƙarfi, dorewa, da sauƙin sarrafawa, shigarwa, da kiyayewa. An gina su daga daidaitaccen -yanke, mai zafi{2}} birgima, tsintsiya, da ƙarfe mai mai, waɗannan tankuna ana walda su sosai don tabbatar da ingancin tsari da tsawon rai. An ƙera su ne don samar da ƙaƙƙarfan kariya ga ruwa mai hana ruwa da kuma sauran abubuwan ciki masu mahimmanci ga aikin na'ura.

Tankuna suna yin gwajin ƙira mai tsauri, suna nuna ikon jure matsin lamba har zuwa 7 psig ba tare da fuskantar hargitsi na dindindin ba da 15 psig ba tare da haɗarin fashewa ba. Wannan ƙwaƙƙwaran gwaji yana tabbatar da cewa tankuna na iya jure wa ƙalubale yanayin aiki, ta yadda za a haɓaka amincin gabaɗaya da amincin tsarin taswira. Ta hanyar sabbin ƙira da ƙaya mafi inganci-, waɗannan tankuna suna taka muhimmiyar rawa wajen kiyaye ayyuka da ingancin na'urorin taswira.

2000 kVA distribution substation transformer oil tank

 

2.4 Taron Karshe

2000 kVA distribution substation transformer assembly

Core da Coil Assembly: Ƙarfafa ginshiƙi tare da ƙarshen ƙarfe mai nauyi don hana karkatar da iska.

Gyaran Wuta: A busar da taransfoma kuma a cika shi da taceccen mai mai hana ruwa a cikin injina yayin da ake ƙarfafa iska ta biyu don fitar da danshi.

Shigar da Tanki: Shigar da tankin mai da aka rufe don ingantaccen zubar da zafi.

Haɗin Wutar Lantarki: Haɗa manyan tarnaƙi da ƙananan ƙarfin lantarki tare da tsarin rarraba na waje.

Ciko Mai da Magani: Zuba man mai mai inganci mai inganci{{0}a cikin tankin transfoma kuma a gudanar da maganin bazuwar don tabbatar da kaddarorin mai.

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

3.47

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

0.02

Wuce

3

Mataki - Gwaje-gwajen alaƙa

/

Dyn1

Dyn1

Wuce

4

A'a -Asar lodi da tashin hankali Yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

0.21

1.833

Wuce

5

Haɓaka Haɓaka Ƙarfin Wutar Lantarki da Inganci

%

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

Haƙuri don impedance shine ± 7.5% Ingantaccen aiki ba kasa da 99.37%

6.30

17.404

19.237

99.43

Wuce

6

Gwajin Karfin Wutar Lantarki

kV

HV: 95kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV): 2 Ur

Duration(s):40

Mitar (HZ): 180

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Gwajin Leaka

kPa

matsa lamba: 50kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground:

LV -HV zuwa Ground:

HV&LV zuwa Ground:

55.0

29.8

36.2

Wuce

10

Gwajin Mai

kV,

mg/kg,

%,

mg/kg,

Ƙarfin Dielectric;

Abubuwan Danshi;

Halin Rushewa;

Furan Analysis ;

Gas Chromatography Analysis

55.1

7.8

0.187

Kasa da ko daidai da 0.1

/

Wuce

 

2000 kVA distribution substation transformer testing
2000 kVA distribution substation transformer test

 

 

04 Shiryawa da jigilar kaya

2000 kVA distribution substation transformer packing
distribution substation transformer transportation

 

 

05 Yanar Gizo da Takaitawa

A taƙaice, an ƙera na'urorin injin mu don samar da ingantacciyar aminci da ingantaccen aiki, ƙarfafa grid ɗin ku tare da ci gaba da aiki mai dorewa. Tare da yanke sabbin sabbin fasahohi na fasaha da tsattsauran kula da inganci, muna tabbatar da tsayayyen mafita na rarraba makamashi don abubuwan more rayuwa na zamani. Zaɓin samfuranmu yana nufin zaɓin aminci da hankali na watsa wutar lantarki na gaba. Jin kyauta don tuntuɓar mu a kowane lokaci don gano yadda mafitarmu za ta iya taimaka muku gina tsarin makamashi mai ƙarfi.